EasyManua.ls Logo

Hirschmann RSPM20-4Z64Z6 Series - EMC and Immunity Specifications

Hirschmann RSPM20-4Z64Z6 Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation RSPM
Release
15
04/2018
31
EMC and immunity
You will find detailed information on the certificates and declarations applying to your device in a separate overview.
See table 2 on page 18.
EMC interference
emission
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Radiated emission
EN 55032 Class A Class A Class A Class A
GL Guidelines EMC 1
FCC 47 CFR Part 15 Class A Class A Class A Class A
EN 61000-6-4 Fulfilled Fulfilled Fulfilled Fulfilled
Conducted emission
EN 55032 DC supply connection Class A Class A Class A Class A
GL Guidelines DC supply connection EMC 1
FCC 47 CFR Part 15 DC supply connection Class A Class A Class A Class A
EN 61000-6-4 DC supply connection Fulfilled Fulfilled Fulfilled Fulfilled
EN 55032 Telecommunication connections Class A Class A Class A Class A
EN 61000-6-4 Telecommunication connections Fulfilled Fulfilled Fulfilled Fulfilled
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge ±4kV ±6kV ±6kV ±8kV
EN 61000-4-2
IEEE C37.90.3
Air discharge ±8kV ±8kV ±8kV ±15kV
Electromagnetic field
EN 61000-4-3 80 MHz ... 3000 MHz 10 V/m 10 V/m 20 V/m 10 V/m