32
Installation RSPM
Release
15
04/2018
IEEE 1613 80 MHz ... 1000 MHz — — — 35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection ±2 kV ±2 kV ±2 kV ±4 kV
EN 61000-4-4
IEEE C37.90.1
Data line ±4 kV ±4 kV ±2 kV ±4 kV
Voltage surges - DC supply connection
EN 61000-4-5 line/ground ±2 kV ±2 kV ±2 kV ±2 kV
IEEE 1613 line/ground — — — ±5 kV
EN 61000-4-5 line/line ±1 kV ±1 kV ±1 kV ±1 kV
Voltage surges - data line
EN 61000-4-5 line/ground ±1 kV ±1 kV ±2 kV ±2 kV
Conducted disturbances
EN 61000-4-6 150 kHz ... 80 MHz 10 V 10 V 10 V 10 V
EMC interference
immunity
Standard
applications
Navy applications Railway
applications
(trackside)
Substation
applications