3-3. How to Initialize the Data (FACTORY SETTING)
1. Select the mode of initialization data to which you want to initialize by [b85].
Japanese version data -----> Set “00” and store
EU version data -----> Set “01” and store
US version data -----> Set “02” and store
2. Set [b84] to “01” to initialize and store.
3. Keep pressing keys at the same time.
(If front case is not closed by the screw, dittcult to press 3keys.)
4. Additionally press key and release key approximately after one second.
5. Keep pressing keys until “d 00” will blink. (Approximately 2 seconds.)
6. Release all the keys after starts blinking.
[c95] ; INV kW code
01;0.2kW , 02;0.4kW , 03;0.75kW (0.5 kW) , 04;1.5kW , 05;2.2kW ,
06;3.7kW(4.0kW) , 07;5.5kW, 08;7.5kW
Initialization end
Release after
“
d 00
”
started blinking
FUNC.
1
2
FUNC.
1
2
STOP
RESET
STOP
RESET
FUNC.
1
2
ON (press)
ON
ON
ON
1s or more
STOP
RESET