“C” Group: Intelligent Terminal Functions
Configuring
Drive Parameters
3–60
Miscellaneous Functions
The following table contains miscellaneous functions not in other function groups.
“C” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
C091 Debug mode enable Displays debug parameters.
Two option codes:
00... Disable
01... Enable
✔ ✔ 00 00
DBG Slct OFF
C101 Up/Down memory
mode selection
Controls speed setpoint for the
inverter after power cycle. Two
option codes:
00... Clear last frequency
(return to default frequency
F001)
01... Keep last frequency
adjusted by UP/DWN
✘ ✔ 00 00
UP/DWN NO-STR
C102 Reset selection Determines response to Reset
input [RST].
Three option codes:
00... Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01... Cancel trip state at signal
OFF transition, stops inverter if
in Run Mode
02... Cancel trip state at input
signal ON transition, no effect
if in Run Mode
✘ ✔ 00 00
RS Slct ON