What to do if Hitachi Inverter shows over current detection at output stage?
- MMalik ChristensenAug 20, 2025
If the Hitachi Inverter experiences over current detection at the output stage, it could be due to a rapidly changing load or a short circuit/earth contact in the motor or motor cable. To resolve this, if fast deceleration is happening, preset the Decel time longer. Also, check the wires if any motor is locked. Reduce the value if high preset torque boost is enabled, and verify if the preset DC injection brake level is high. Finally, check for any CT malfunction or noise.