EasyManua.ls Logo

Hitachi L300P Series - 4 The Check of Control Power Supply Voltage and a Control Signal; Control Power Supply Voltage; Control Signal

Hitachi L300P Series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-1
4. The check of control power supply voltage and a control signal
4.1 Control power supply
Measurement place
Item
Tolerance level
+ -
PV5 +5V power supply
4.5V - 5.5V J1 connector 25,16pin Control terminal L
PV12 +12V power supply
10.8V - 13.2V J1 connector 7pin Control terminal L
NV12 -12V power supply -13.2V - -10.8V J1 connector 5pin Control terminal L
PV24 24V power supply
21.6V - 26.4V
J1 connector 3,4pin,
Control terminal P24
Control terminal CM1
4.2 Control signal
Signal Measurement place The contents of operation Observation waveform
VDC J1 connector 12pin-L
A main circuit direct-current voltage
detected signal
VDC=6.396V/400V*VPN(200Vclass)
VDC=6.396V/800V*VPN(400Vclass)
Direct-current voltage
IUF
IWF
J1 connector 9pin-L
J1 connector 8pin-L
A motor current detected signal
At the time of inverter rated load: About
3.3 V peak
TRIP J1 connector 21pin-L
The signal at the time of carrying out a
trip by the trip factor which a gate array
judges (P3-1 reference)
Normal : 5V(H)
Inside of a trip : about 0.3V(L)
Direct-current voltage
PHF J1 connector 22pin-L
Phase failure protection detected
signal
Normal :5V(H)
Phase failure detection :about0.5V(L)
Direct-current voltage
IPL J1 connector 11pin-L
The instantaneous power failure signal
of R0-T0 part
Power On : about0.5V(L)
Power Off : 5V(H)
Direct-current voltage
GS J1 connector 20pin-L
Power-module protection
Under operation : about 5V(H)
Under a stop : about 0.5V(L)
Direct-current voltage
US
VS
WS
J1 connector 17pin-L
J1 connector 18pin-L
J1 connector 19pin-L
PWM signal
Upper arm ON : about 3.5V(L)
lower arm ON : about 5V(H)
GS J1 connector 30pin-L
The trip distinguished by GA is canceled.
Normal : about 5V(H)
Under reset : about 0.5V(L)
0V
-3.3V
3.3V
3.5V
5V
0V
Upper arm ON
Lower arm ON
Reset Reset
5V
0.5V
0V

Other manuals for Hitachi L300P Series