Chapter 4 List of Data Settings 
 
4 - 8 
 
Code  Function name  Monitored data or setting 
Default 
Setting 
during 
operation 
(allowed or 
not
 
Change 
during 
operation 
(allowed or 
not
_FF 
Others 
b034  Run/power-on warning time 
0. to 9999. (0 to 99990), 
1000 to 6553 
0.  ¯  { 
b035  Rotational direction restriction 
00 (enabling both forward and reverse rotations), 
01 (enabling only forward rotation),   
02 
00  ¯  ¯ 
b036  Reduced voltage start selection 
0 (minimum reduced voltage start time) to 
255 
6  ¯  { 
b037  Function code display restriction 
00 (full display), 01 (function-specific display), 
02 (user setting), 03 (data comparison display),   
04 
04  ¯  { 
b038 Initial-screen selection 
00 (screen displayed when the STR key was pressed last), 
01 
01  ¯  { 
b039 
Automatic use
-parameter setting 
function enable 
00 (disabling), 01 (enabling)  00  ¯  { 
Torque limitation 
b040 Torque limit selection 
00 (quadrant-specific setting), 01 (switching by terminal), 
02 
00  ¯  { 
b041 
Torque limit (1) (forward-driving in 
4-
 
0. to 150. (%), no (disabling torque limitation)  120.  ¯  { 
b042 
Torque limit (2) (reverse-regenerating in 
4-quadrant mode
 
0. to 150. (%), no (disabling torque limitation)  120.  ¯  { 
b043 
Torque limit (3) (reverse-driving in 
4-quadrant mode
 
0. to 150. (%), no (disabling torque limitation)  120.  ¯  { 
b044 
Torque limit (4) (forward-
egenerating in 
4-quadrant mode
 
0. to 150. (%), no (disabling torque limitation)  120.  ¯  { 
b045 Tor
ue limit LADSTOP enable  00 
00  ¯  {
b046  Reverse Run protection enable  00 
01  ¯  {
Non-stop operation at momentary 
power failure 
b050 
Controller deceleration and stop on 
power loss 
00 (disabling), 01 (nonstop deceleration to stop), 
02 (DC voltage constant control, with resume),   
03 
00  ¯  ¯ 
b051 
DC bus voltage trigger level during 
power loss 
0.0 to 999.9, 1000. (V) 
220.0/ 
440.0 
¯  ¯ 
b052 
Ove
-voltage threshold during power 
loss 
0.0 to 999.9, 1000. (V) 
360.0/ 
720.0 
¯  ¯ 
b053 
Deceleration time setting during power 
loss 
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)  1.00  ¯  ¯ 
b054 
Initial output frequency decrease during 
ower loss 
0.00 to 10.00 (Hz)  0.00  ¯  ¯ 
b055 
Proportional gain setting for nonstop 
operation at power loss 
0.00 to 2.55  0.20  {  { 
b056 
Integral time setting for nonstop 
operation at power loss 
0.000 to 9.999 /10.00 to 65.53 (s)  0.100  {  { 
Window comparator 
b060 
Maximum-limit level of window 
comparators O 
0. to 100. (lower limit : b061 + b062 *2) (%)  100  {  { 
b061 
Minimum-limit level of window 
comparators O 
0. to 100. (lower limit : b060 - b062 * 2) (%)  0  {  { 
b062 
H
steresis width of window 
com
arators O 
0. to 10. (lower limit : b061 - b062 / 2) (%)  0  {  { 
b063 
Maximum-limit level of window 
com
arators OI 
0. to 100. (lower limit : b064 + b066 *2) (%)  100  {  { 
b064 
Minimum-limit level of window 
comparators OI 
0. to 100. (lower limit : b063 - b066 *2) (%)  0  {  { 
b065 
Hysteresis width of window 
comparators OI 
0. to 10. (lower limit : b063 - b064 / 2) (%)  0  {  { 
b066 
Maximum-limit level of window 
comparators OI 
-100. to 100. (lower limit : b067 + b068* 2) (%)  100  {  { 
b067 
Minimum-limit level of window 
comparators O/OI/O2 
-100. to 100. (lower limit : b066 - b068 * 2) (%)  -100  {  { 
b068 
Hysteresis width of window 
com
arators O/OI/O2 
0. to 10. (lower limit : b066 - b067 / 2) (%)  0  {  { 
b070  Operation level at O disconnection  0. to 100.
eration level at OI disconnection 0. to 100.
no  ¯  {
b072  Operation level at O2 disconnection  -100. to 100.
no  ¯  {
(Note)<>indicate the setting range of 90 to 160kW