Chapter 4 List of Data Settings
4 - 9
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
_FF
Others
b078 Cumulative input power data clearance Clearance b
00 { {
b079 Cumulative input power displa
1. to 1000. 1. { {
b082 Start frequenc
0.50 ¯ {
b083 Carrier frequency setting
0.5 to 12.0 (kHz) (subject to derating)
<0.5 to 12.0
>
3.0 ¯ ¯
b084
Initialization mode (parameters or trip
histor
00 (clearing the trip history), 01 (initializing the data),
02
0.1 to 99.0 1.0 { {
b087 STOP key enable
00 (enabling), 01 (disabling),
02
00 ¯ {
b088 Restart mode after FRS
00 (starting with 0 Hz),
01 (starting with matching frequency),
02
00 ¯ {
b089 Automatic carrier fre
reduction 00: invalid, 01: valid 00 ¯ ¯
b090 D
00 ¯ {
b092 Cooling fan control
00 (always operating the fan), 01 (operating the fan only
during inverter operation [including 5 minutes after
01 ¯ {
b095 Dynamic braking control
00 (disabling),
01 (enabling [disabling while the motor is topped]),
02
also while the motor is topped]
01 ¯ {
b096 Dynamic braking activation level 330 to 380, 660 to 760(V)
360/
720
¯ {
b098 Thermistor for thermal protection control
00 (disabling the thermistor),
01 (enabling the thermistor with PTC),
02
00 ¯ {
b099 Thermal protection level settin
3000. ¯ {
Free setting of V/f characteristic
b100 Free-settin
0.0 ¯ ¯
Others
b130 Overvoltage suppression enable
00 (disabling the restraint), 01 (controlled deceleration),
02
00 ¯ {
b131 Overvoltage suppression level
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V
class model
380/
760
¯ {
b132
Acceleration and deceleration rate at
overvolta
e suppression
0.10 to 30.00 (s) 1.00 ¯ {
b133 Overvolta
e suppression propotional
ain 0.00 to 2.55 0.50 { {
b134 Overvolta
ral time 0.000 to 9.999 / 10.00 to 65.53
0.060 { {
(Note)<>indicate the setting range of 90 to 160kW