Chapter 4 List of Data Settings
4 - 11
Code Function name Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
_FF
Intelligent output terminals
C021 Terminal [11] function
00 (RUN: running), 01 (FA1: constant-speed reached),
02 (FA2: set frequency overreached),
03 (OL: overload notice advance signal (1)),
04 (OD: output deviation for PID control),
05 (AL: alarm signal),
06 (FA3: set frequency reached), 07 (OTQ: over-torque),
08 (IP: instantaneous power failure),
09 (UV: undervoltage), 10 (TRQ: torque limited),
11 (RNT: operation time over),
12 (ONT: plug-in time over),
13 (THM: thermal alarm signal),
21 (ZS: 0 Hz detection signal),
24 (FA4: set frequency overreached 2),
25 (FA5: set frequency reached 2),
26 (OL2: overload notice advance signal (2)),
27 (Odc: Analog O disconnection detection),
28 (OIDc: Analog OI disconnection detection),
29 (O2Dc: Analog O2 disconnection detection),
31 (FBV: PID feedback comparison),
32 (NDc: communication line disconnection),
33 (LOG1: logical operation result 1),
34 (LOG2: logical operation result 2),
35 (LOG3: logical operation result 3),
36 (LOG4: logical operation result 4),
37 (LOG5: logical operation result 5),
38 (LOG6: logical operation result 6),
39 (WAC: capacitor life warning),
40 (WAF: cooling-fan speed drop),
41 (FR: starting contact signal),
42 (OHF: heat sink overheat warning),
43 (LOC: low-current indication signal),
44 (M01: general-purpose output 1),
45 (M02: general-purpose output 2),
46 (M03: general-purpose output 3),
47 (M04: general-purpose output 4),
48 (M05: general-purpose output 5),
49 (M06: general-purpose output 6),
50 (IRDY: inverter ready), 51 (FWR: forward rotation),
52 (RVR: reverse rotation), 53 (MJA: major failure),
54(WCO: window comparator O),
55(WCOI: window comparator OI),
56 (WCO2: window comparator O2)
(When alarm code output is selected for "C062", functions
"AC0" to "AC2" or "AC0" to "AC3" [ACn: alarm code
output] are forcibly assigned to intelligent output terminals
11 to 13 or 11 to 14, respectivel
01 ¯ ¯
C022 Terminal [12] function 00 ¯ ¯
C023 Terminal [13] function 03 ¯ ¯
C024 Terminal [14] function 07 ¯ ¯
C025 Terminal [15] function 40 ¯ ¯
C026 Alarm relay terminal function 05 ¯ ¯
Analog monitoring
C027 [FM] siginal selection
00 (output frequency), 01 (output current),
02 (output torque), 03 (digital output frequency),
04 (output voltage), 05 (input power),
06 (electronic thermal overload), 07 (LAD frequency),
08 (digital current monitoring), 09 (motor temperature),
10 (heat sink temperature),
12