WORKING RANGE
1-48
TCI-20007-rev.1
7. Working Range
Power Supply
Working Voltage: 90% to 110% of the Rated Voltage
Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal
Starting Voltage: Higher than 85% of the Rated Voltage
Temperature Range
The temperature range are given in the following table.
Temperature
(
o
C)
Maximum Minimum
Cooling Operation
Indoor 30 DB 21.5 DB
Outdoor 43 DB * -5 DB *
Heating Operation
Indoor 25 DB 17 DB
Outdoor 15.5 WB * -10 WB *
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.