OPTIONAL ACCESSORIES
1-54
TCI-20007-rev.1
Model
Item
For Ceiling Type
DUPC-63K1 DUPC-71K1 DUPC-160K1
Applicable Indoor Unit Model (RPC-**FSR) 1.5 2.0 2.5 to 6.0
Maximum Lift for Drain-Up mm 600 (from the upper side of the indoor unit)
Power Source DC13V
Power Consumption W 4.2 or less
Drain Piping Connection PVC Tube, VP25
Diameter of
Field-processed Ref. Pipe
(Flare Nut Connection)
mm
Gas
A
12.7 12.7 15.88
Liquid
B
6.35 6.35 9.52
Applicable Refrigerant R410A
Weight 3.5 kg
Accessory
Drain Hose, Pipe for Drain-Up, Ref. Gas/Liquid Pipes for Upper Side of
Indoor Unit, Clamp, Insulation, Screws, Installation and Maintenance
Manual
Protection Device Float Switch (for Alarm)
Antimicrobial Agent Silver-Ionic Antimicrobial Agent Using Dissoluble Glass
Restrictions for Installation
1. When viewed from the front, the position of drain-up pipe must be on
the right side of the indoor unit.
2. Ref. gas/liquid pipes (accessory) must be attached to the upper side
of the indoor unit.
Maintenance
Cleaning of Water tank: once a year
Cleaning of Pump: once a year
Cleaning of Float Switch: Once a year
Replacement Cycles for Antimicrobial Agent: At 10.000 hours (approx. 5
years)
NOTES:
1. Before installing the indoor unit, provide a hole (
300 mm) for piping connection. Use the accessory
refrigerant gas/liquid pipes and pipe for drain-up to mount the drain-up mechanism.
2. PVC Tube (VP25) must be used for the drain connection.
3. Lower the indoor unit 10mm when the drain-up mechanism is installed.
(In case of inclination beyond 10mm, it’ll be water leakage or abnormal stoppage.)
4. Do not provide a trap or riser portion for the drain pipe. Install the pipe with a falling gradient of 1/25 ~
1/100.
5. Cover the drain pipe and refrigerant gas/liquid pipes with insulations in order to avoid dew condensation.
6. Do not take out and put in connectors frequently. Constant taking out and putting in can lead to a PCB
malfunction.
7. Install the indoor unit in a horizontal position only. An Inclined unit can result in water leakage or abnormal
stoppage.
8. Before shipment, the accessory drain-up pipe’s height from the upper surface of the unit is set to 600 mm,
which can be lowered to 150 mm. If making the height lower, cut the pipe on site.
9.Afterinstallingthedrain-upmechanism,soundofdrainwaterowingcanbeheard.Thisisthesound
made when the drain water is discharged and so there are no safety concerns.
8.2.3 Motion Sensor Kit: SOR-NEP
Refer to chapter 1.4.13 for details.