S1 series standard inverter
-150-
Detailed parameter description
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
Communication
processing action
0x00–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
P17 group State-check function
Display current set frequency of the inverter.
Range: 0.00Hz–P00.03
Display current output frequency of the inverter.
Range: 0.00Hz–P00.03
Ramps reference
frequency
Display current ramps reference frequency of the
inverter.
Range: 0.00Hz–P00.03
Display current output voltage of the inverter.
Range: 0–1200V
Display the valid value of current output current of
the inverter.
Range: 0.0–5000.0A
Display current motor speed.
Range: 0–65535RPM
Display current torque current of the inverter.
Range: -3000.0–3000.0A
Display current exciting current of the inverter.
Range: -3000.0–3000.0A
Display current motor power; 100% relative to
rated motor power, positive value is motoring
state, negative value is generating state.
Range: -300.0–300.0% (relative to rated motor
power)
Display current output torque of the inverter;