S1 series standard inverter
-55-
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P00.01
Running command channel
0: Keypad
1: Terminal
2: Communication
1
P00.15
Motor parameter autotuning
0: No operation
1: Rotary autotuning; carry out
comprehensive motor parameter
autotuning; rotary autotuning is used in
cases where high control precision is
required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial
autotuning) ; when current motor is motor
1, only P02.06, P02.07 and P02.08 will
be autotuned; when current motor is
motor 2, only P12.06, P12.07 and P12.08
will be autotuned.
0
P02.01
Rated power of
asynchronous motor 1
0.13000.0kW
Depend
on model
P02.02
Rated frequency of
asynchronous motor 1
0.01HzP00.03 (Max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
136000rpm
Depend
on model
P02.04
Rated voltage of
asynchronous motor 1
01200V
Depend
on model
P02.05
Rated current of
asynchronous motor 1
0.86000.0A
Depend
on model
P02.06
Stator resistance of
asynchronous motor 1
0.001–65.53
Depend
on model
P02.07
Rotor resistance of
asynchronous motor 1
0.001–65.53
Depend
on model
P02.08
Leakage inductance of
asynchronous motor 1
0.16553.5mH
Depend
on model
P02.09
Mutual inductance of
asynchronous motor 1
0.16553.5mH
Depend
on model

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi S1 Series and is the answer not in the manual?

Hitachi S1 Series Specifications

General IconGeneral
Output Frequency0 - 400 Hz
Overload Capacity150% for 60 seconds
Frequency50/60 Hz
Control MethodSensorless Vector Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS485, Modbus RTU
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC (Matches Input Voltage)
Cooling MethodFan Cooled