S1 series standard inverter
-88-
Function
code
Name
Detailed parameter description
Default
value
1: No function
2: AI1
3: AI2
P00.11
Acceleration time 1
0.03600.0s
Depend
on model
P00.12
Deceleration time 1
0.03600.0s
Depend
on model
P05.01
P05.06
Digital input function
selection
26: Wobbling frequency pause (stop at
current frequency)
27: Wobbling frequency reset (revert to
center frequency)
/
P08.15
Amplitude of wobbling
frequency
0.0100.0% (relative to set frequency)
0.0%
P08.16
Amplitude of jump frequency
0.050.0% (relative to amplitude of
wobbling frequency)
0.0%
P08.17
Rise time of wobbling
frequency
0.13600.0s
5.0s
P08.18
Descend time of wobbling
frequency
0.13600.0s
5.0s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi S1 Series and is the answer not in the manual?

Hitachi S1 Series Specifications

General IconGeneral
Output Frequency0 - 400 Hz
Overload Capacity150% for 60 seconds
Frequency50/60 Hz
Control MethodSensorless Vector Control
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS485, Modbus RTU
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC (Matches Input Voltage)
Cooling MethodFan Cooled