2-18
Chapter 2
Installation and Wiring
Recommended terminals for wiring
The following ferrule terminals are recommended for
signal cable for easy wiring and improved reliability of
connectivity.
Ferrule terminal with sleeves
*) Manufacturer: Phoenix Contact
Wiring procedure
1. Open the insertion hole of the control circuit terminal
block into the socket with a slotted screwdriver (with a
wide of 2.5mm or less).
2. Insert the wire or ferrule terminal into the wire
insertion hole (round) while screwing up with a slotted
screwdriver.
The control circuit terminal adopts screw type wiring
terminal blocks.
Crimping tool: CRIMPFOX UD 6-4 or CRIMPFOX ZA 3
Even for pulling out the wire from the socket with a
slotted screwdriver (the insertion hole will be opened).
Power cable size
mm
2
(AWG)
Ferrule terminal
model*
L1 [mm]
L2 [mm]
d [mm]
D [mm]
0.25 (24)
AI 0,25-8YE
4
12.5
0.8
2.0
0.34 (22)
AI 0,34-8TQ
4
12.5
0.8
2.0
0.5 (20)
AI 0,5-8WH
4
14
1.1
2.5
2.5mm
Insert the wire or ferrule terminal into the wire
insertion hole while screwing up with a slotted
screwdriver.