EasyManua.ls Logo

Hitachi SH1 Series - Analog Input;Output Configuration

Hitachi SH1 Series
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-5
Chapter 3
Operation Setting and Examples of I/O Adjustment
Example for adjusting I/O terminals 1
3.9 Adjust the analog input (Ai1/Ai2)
E.g.1) Adjust operation (The frequency reference is set by [Ai1] )
The frequency reference range corresponding to the analog
input can be set arbitrarily.
Parameter
Parameter
Details
Ai1
Ai2
[Cb-03]
[Cb-13]
Set the start frequency when the analog
input is [Cb-05]. Set the ratio (%) with the
maximum frequency as 100%.
[Cb-04]
[Cb-14]
Set the end frequency when the analog input
is [Cb-06]. Set the ratio (%) with the
maximum frequency as 100%.
[Cb-05]
[Cb-15]
Set the start ratio (%) between analog input
0 to 10 VDC/0 to 20 mA.
[Cb-06]
[Cb-16]
Set the end ratio (%) between analog input 0
to 10 VDC/0 to 20 mA.
[Cb-07]
[Cb-17]
Sets whether the frequency reference from
0% to [Cb-05]/[Cb-15] is set to 0% or
[Cb-03]/[Cb-13].
E.g.2) Fine setting (The frequency reference is set by [Ai1])
If there is a deviation between the analog input and the
frequency reference in the above [Cb-03] to [Cb-06]
adjustment, fine adjustment is possible as follows.
At this time, set [Cb-03] to [Cb-06] to the default values as
possible. Typically, the gain / bias is adjusted within a few
percent.
Parameter
Parameter
Details
Ai1
Ai2
[Cb-30]
[Cb-32]
Fine adjustment of the analog input 0 V / 20
mA point is performed by adding the bias
value to the frequency reference. Set the
ratio (%) with the Maximum frequency as
100%.
[Cb-31]
[Cb-33]
As shown above figure, fine adjustment is
performed by multiplying the slope of the
reference line by the gain. Set the ratio (%)
based on the (Maximum frequency / analog
input (10V / 20mA)) = 100%.
*) The voltage/current input is switched by the slide switch on the
board.
*) For the adjustment of Ai2, read the above parameter Ai1 as Ai2.
Example for adjusting I/O terminals 2
3.10 Adjust the analog output (Ao1/Ao2/FM)
E.g.) Adjust operation ([Ao1] outputs the output frequency )
Adjust the actual analog output by adding the bias [Cd-23] to
the analog output when the output data is 0%.
Then, adjust the slope by multiplying the gain [Cd-24] to the
reference line that (Analog output(10V/20mA)/ output data
full scale) is 100%, adjust the analog output when the output
data is 100%.
Parameter
Parameter
Details
Ao1
Ao2
[Cd-23]
[Cd-33]
The actual analog output is adjusted
by adding a bias to the analog output
when the output data is 0%. Set the
ratio (%) based on analog output
(10V / 20mA) = 100%.
[Cd-24]
[Cd-34]
The {analog output (10V / 20mA) /
output data full scale} = 100% is used
as the reference line, and the actual
analog output is adjusted by
multiplying the slope by a gain.
The output form of the FM terminal can select PWM output or
digital frequency output by [Cd-01].
At PWM output, the pulse duty = t/T (%) is constant (T = 6.4
ms), and t/T (%) = 100% at full scale of output data. At digital
frequency output, t/T (%) is fixed at 50%, and the output pulse
frequency at full scale output data is set by [Cd-02].
Parameter
Details
FM
[Cd-13]
Adjust the actual pulse output by adding a bias to
the pulse output when the output data is 0%.
For PWM output, set the ratio (%) based on the
output duty (t/T) (%) = 100%. For digital frequency
output, set the ratio based on [Cd-02] Set
frequency = 100% (%).
[Cd-14]
{Pulse output (%) /Output data full scale = 100%} is
used as the reference line, and the actual pulse
output is adjusted by multiplying the slope by a
gain.
*) Analog output terminals Ao1/Ao2 can be switched to voltage or current
output with the slide Switch on the control circuit terminal.
Factory setting is Ao1=voltage output and Ao2=current output.
*) Adjustment for analog output Ao1/Ao2/FM are set with [Cd-01] to
[Cd-35].
(Note: In Ver2.02 or later, the initial value of Ao2 is 4 to 20 mA current
output, and the [Cd-34] setting value has been changed from 100% to
80%. When using the analog output, be sure to check the related
parameters and the slide switch on the board. )
Output full scale
( For output
frequency, the
maximum
frequency is
100% )
100%
0%
Parallel slide
Output
range
[Cd-23]=-50.0(%)
[Cd-23]=0.0(%)
0%
50%
-50%
[Cd-23]=50.0(%)
[Cd-24]=200.0(%)
[Cd-24]=100.0(%)
[Cd-24]=50.0(%)
[Cd-24]= -50.0(%)
Analog (10V/20mA)
Or Pulse output (%)
Reference Line
Change
the Slope
angle
Maximum frequency
100(%)
0%
Parallel slide
[Cb-30]=-10.0(%)
[Cb-30]=0.0(%)
0%
10%
-10%
Change the Slope angle
[Cb-30]=10.0(%)
[Cb-31]=110.0(%)
[Cb-31]=90.0(%)
[Cb-31]=100.0(%)
Analog input
10V/20mA = 100(%)
Reference Line
Maximum frequency
100%
[Cb-04]
[Cb-03]
0%
[Cb-05]
[Cb-06]
100%
(0V/0mA)
(10V/20mA)
Analog input (%)
While setting [Cb-07] = 00,
the frequency reference
from 0% to [Cb-05] will be
set by [Cb-03].
(When [Cb-07] = 01, the
frequency reference from
0% to [Cb-05] is 0Hz)

Related product manuals