4.2.59 Intelligent output terminal a/b (NO/NC) selection 
The intelligent output terminal a/b (NO/NC) selection function 
allows you to specify a-contact or b-contact output for each of 
the intelligent output terminals [11] to [15] and the alarm relay 
terminal. 
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal 
is used for relay output. 
Item Function code Data Description 
00 
a-contact (NO) 
Terminal active state  C031 to C035 
01 
b-contact (NC) 
00 
a-contact (NO) 
Alarm relay active state  C036 
01 
b-contact (NC) 
 
- An a-contact turns on the output signal when closed and turns it off when opened. 
- A b-contact turns on the output signal when opened and turns it off when closed. 
 
(1) Specifications of intelligent output terminals [11] to [15] 
Intelligent output terminals [11] to [15] have the following specifications: 
 
15 CM2 …  … 11 
 
 
 
Setting of C031 to C035  Power supply Output signal 
ON 
ON 
OFF 
00 
(a-contact) 
OFF  - 
ON 
ON 
OFF 
01 
(b-contact) 
OFF  - 
 
(2) Specifications of alarm relay terminal   
The alarm relay terminal uses a normally-closed (NC) contact that operates as described below. 
 
AL0 AL1 AL2 
 
 
 
 
Example of operation as an alarm output terminal 
Output terminal stateSetting 
of C036 
Power 
supply 
Inverter 
status 
AL1-AL0 AL2-AL0
Error Closed Open 
ON 
Normal Open Closed
00 
OFF  - Open Closed
Error Open Closed
ON 
Normal Closed Open 
01 
(default) 
OFF  - Open Closed
C031 to C035: Terminal [11] to [15] active state 
C036: Alarm relay active state 
Related code 
Electric characteristics 
(Between each terminal and CM2) 
Voltage drop when turned on: 4 V or less
Allowable maximum voltage: 27 VDC 
Allowable maximum current: 50 mA 
 
Inside the 
inverter 
Inside the 
inverter 
  Resistance load  Inductive load 
Maximum contact 
capacity 
250 VAC, 2 A 
30 VDC, 8 A 
250 VAC, 0.2 A
30 VDC, 0.6 A 
AL1-AL0
Minimum contact 
capacity 
100 V AC, 10 mA 
5 VDC, 100 mA 
Maximum contact 
capacity 
250 VAC, 1A 
30 VDC, 1A 
250 VAC, 0.2 A
30 VDC, 0.2 A 
AL2-AL0
Minimum contact 
capacity 
100 VAC, 10 mA 
5 VDC, 100 mA