4.2.60 Running signal (RUN) 
While the inverter is operating, it outputs the running (RUN) 
signal via an intelligent output terminal ([11] to [15]) or the alarm 
relay terminal. 
To use this signal function, assign function "00" (RUN) to one of the intelligent output terminals [11] to [15] 
(C021 to C025) and the alarm relay terminal (C026). 
The inverter outputs the RUN signal even while operating the DC brake. The following figure shows a 
timing chart for the signal output: 
 
 
 
 
 
 
 
 
 
4.2.61 Frequency arrival signals (FA1, FA2, FA3, FA4, and FA5) 
The inverter outputs a frequency-arrival signal when the inverter 
output frequency reaches a set frequency. 
When using the inverter for a lift, use the frequency-arrival signal as   
a trigger to start braking. Use the over-torque signal as the trigger to 
stop braking. 
Assign the following functions to five of the intelligent output terminals 
[11] to [15] (C021 to C025) and the alarm relay terminal (C026): 
"01" (FA1: constant-speed reached), "02" (FA2: set frequency overreached), "06" (FA3: set frequency 
reached), "24" (FA4: set frequency overreached 2), and "25" (FA5: set frequency reached 2) 
The hysteresis of each frequency-arrival signal is as follows: 
When the signal is on: ("set frequency" - "1% of maximum frequency") (Hz) 
When the signal is off: ("set frequency" - "2% of maximum frequency") (Hz) 
 
The signal hysteresis at acceleration with function "06" (FA3) or "25" (FA5) set is as follows: 
When the signal is on: ("set frequency" - "1% of maximum frequency") (Hz) 
When the signal is off: ("set frequency" + "2% of maximum frequency") (Hz) 
 
The signal hysteresis at deceleration with function "06" (FA3) or "25" (FA5) set is as follows: 
When the signal is on: ("set frequency" + "1% of maximum frequency") (Hz) 
When the signal is off: ("set frequency" - "2% of maximum frequency") (Hz) 
 
Item  Function code Range of data  Description 
0.0 (Hz)  Disabling the output of frequency
Frequency arrival setting for 
accel./Frequency arrival setting 
for acceleration (2) 
C042/C045 
0.01 to 99.99/ 
  100.0 to 400.0 (Hz) 
Enabling the output of frequency
0.0 (Hz)  Disabling the output of frequency
Frequency arrival setting for 
decel./Frequency arrival setting 
for deceleration (2) 
C043/C046 
0.01 to 99.99/ 
  100.0 to 400.0 (Hz) 
Enabling the output of frequency
 
C021 to C025: Terminal [11] to [15] functions 
Related code 
Output frequency 
RUN 
FW 
C021 to C025: Terminal [11] to [15] functions
C042: Frequency arrival setting for accel. 
C043: Frequency arrival setting for decel. 
C045: Frequency arrival setting for 
acceleration (2) 
C046: Frequency arrival setting for 
deceleration (2) 