Chapter 8 List of Data Settings
 
8 - 9 
 
Code  Function name  Monitored data or setting  Default 
Setting 
during 
operation 
(allowed or 
not) 
Change 
during 
operation 
(allowed or 
not) 
Page
C001  Terminal [1] function (*2) 
18 
(*2) 
¯  { 
C002  Terminal [2] function  16 
¯  { 
C003  Terminal [3] function (*2) 
06 
(*2) 
¯  { 
C004  Terminal [4] function  11 
¯  { 
C005  Terminal [5] function  09 
¯  { 
C006  Terminal [6] function  6 
¯  { 
C007  Terminal [7] function  11 
¯  { 
C008  Terminal [8] function 
01 (RV: Reverse RUN), 02 (CF1: Multispeed 1 setting), 03 (CF2: Multispeed 2 setting), 
04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG: Jogging), 07 
(DB: external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH: 2-stage 
acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external trip), 13 (USP: 
unattended start protection), 14: (CS: commercial power source enable), 15 (SFT: 
software lock), 16 (AT: analog input voltage/current select), 17 (SET3: 3rd motor 
control), 18 (RS: reset), 20 (STA: starting by 3-wire input), 21 (STP: stopping by 3-wire 
input), 22 (F/R: forward/reverse switching by 3-wire input), 23 (PID: PID disable), 24 
(PIDC: PID reset), 26 (CAS: control gain setting), 27 (UP: remote control UP function), 
28 (DWN: remote control DOWN function), 29 (DWN: remote control data clearing), 31 
(OPE: forcible operation), 32 (SF1: multispeed bit 1), 33 (SF2: multispeed bit 2), 34 
(SF3: multispeed bit 3), 35 (SF4: multispeed bit 4), 36 (SF5: multispeed bit 5), 37 (SF6: 
multispeed bit 6), 38 (SF7: multispeed bit 7), 39 (OLR: overload restriction selection), 40 
(TL: torque limit enable), 41 (TRQ1: torque limit selection bit 1), 42 (TRQ2: torque limit 
selection bit 2), 43 (PPI: P/PI mode selection), 44 (BOK: braking confirmation), 45 (ORT: 
orientation), 46 (LAC: LAD cancellation), 47 (PCLR: clearance of position deviation), 48 
(STAT: pulse train position command input enable), 50 (ADD: trigger for frequency 
addition [A145]), 51 (F-TM: forcible-terminal operation), 52 (ATR: permission of torque 
command input), 53 (KHC: cumulative power clearance), 54 (SON: servo-on), 55 (FOC: 
forcing), 56 (MI1: general-purpose input 1), 57 (MI2: general-purpose input 2), 58 (MI3: 
general-purpose input 3), 59 (MI4: general-purpose input 4), 60 (MI5: general-purpose 
input 5), 61 (MI6: general-purpose input 6), 62 (MI7: general-purpose input 7), 63 (MI8: 
general-purpose input 8), 65 (AHD: analog command holding), 66 (CP1: multistage 
position settings selection 1 ), 67 (CP2: multistage position settings selection 2), 68 
(CP3: multistage position settings selection 3), 69 (ORL: Zero-return limit function), 70 
(ORG: Zero-return trigger function), 71 (FOT: forward drive stop), 72 (ROT: reverse drive 
stop), 73 (SPD: speed / position switching), 74 (PCNT: pulse counter), 75 (PCC: pulse 
counter clear), no (NO: no assignment) 
9 
¯  { 
4-46
C011  Terminal [1] active state  00 (NO) / 01 (NC)  00 
¯  { 
C012  Terminal [2] active state  00 (NO) / 01 (NC)  00 
¯  { 
C013  Terminal [3] active state  00 (NO) / 01 (NC)  00 
¯  { 
C014  Terminal [4] active state  00 (NO) / 01 (NC)  00 
¯  { 
C015  Terminal [5] active state  00 (NO) / 01 (NC)  00 
¯  { 
C016  Terminal [6] active state  00 (NO) / 01 (NC)  00 
¯  { 
C017  Terminal [7] active state  00 (NO) / 01 (NC)  00 
¯  { 
C018  Terminal [8] active state  00 (NO) / 01 (NC)  00 
¯  { 
Intelligent input terminals 
C019  Terminal [FW] active state  00 (NO) / 01 (NC)  00 
¯  { 
4-47
*2  When the emergency stop function is enabled (SW1 = ON), "18" (RS) and "64" (EMR) are forcibly written to parameters "C001" and "C003", respectively. (You cannot arbitrarily write "64" to 
"C001".) If the SW1 signal is turned off and then turned on, "no" (no assignment) is set in parameter "C003".