Item
CBSS/CBSL
controller
chassis
DBS/DBL drive
tray Notes
Altitude Operating (m) (
5
) to 3,050
(Environmental temperature: 10°C
to 28°C)
to 950 (Environmental
temperature: 10°C to 40°C)
-
Non-operating (m) -60 to 12,000 -60 to 12,000
Gaseous
contamin
ants
4
Operating G1 classication
levels
G1
classication
levels
-
Non-operating G1 classication
levels
G1
classication
levels
Transport/storage - -
Acoustic
noise
LpAm
6, 7
(dB)
Operating 60 (Environmental temperature:
32°C or less)
1
-
Standby 55
Noise
level (dB)
Operating
(Recommended)
90 or less
3
-
Notes:
1. The system internal temperature controls the rotating speed of the fan. This value
might be exceeded if the maximum load continues under high temperature
environment or if a failure occurs in the system.
2. Sound pressure level [LA] changes from 66dB to 75dB according to the ambient
temperature, drive conguration, and operating status. The maximum value can
reach 79dB during maintenance procedure for failed ENC or power supply unit.
3. Fire-suppression systems and pneumatic sirens can generate high levels of
acoustic noise and aect system performance. It can also cause vibrations to the
hard disk drives (HDD) in the storage systems resulting in I/O errors, performance
degradation in and to some extent damage to the HDDs. The noise level tolerance
of HDDs may vary among dierent models, designs, capacities and
manufacturers. The recommended acoustic noise level for an operating
environment is 90dB or less in order to ensure reliable operations when placing a
Hitachi Vantara storage system two meters from the source of the noise.
Technical specications
Chapter 2: Hardware components and specications
Hitachi Virtual Storage Platform G130 Hardware Reference Guide 17