Item
CBSS/CBSL
controller
chassis
DBS/DBL drive
tray Notes
Altitude Operating (m) (
5
) to 3,050
(Environmental temperature: 10°C
to 28°C)
to 950 (Environmental
temperature: 10°C to 40°C)
-
Non-operating (m) -60 to 12,000 -60 to 12,000
Gaseous
contamin
ants
4
Operating G1 classication
levels
G1
classication
levels
-
Non-operating G1 classication
levels
G1
classication
levels
Transport/storage - -
Acoustic
noise
LpAm
6, 7
(dB)
Operating 60 (Environmental temperature:
32°C or less)
1
-
Standby 55
Noise
level (dB)
Operating
(Recommended)
90 or less
3
-
Notes:
1. The system internal temperature controls the rotating speed of the fan. This value
might be exceeded if the maximum load continues under high temperature
environment or if a failure occurs in the system.
2. Sound pressure level [LA] changes from 66dB to 75dB according to the ambient
temperature, drive conguration, and operating status. The maximum value can
reach 79dB during maintenance procedure for failed ENC or power supply unit.
3. Fire-suppression systems and pneumatic sirens can generate high levels of
acoustic noise and aect system performance. It can also cause vibrations to the
hard disk drives (HDD) in the storage systems resulting in I/O errors, performance
degradation in and to some extent damage to the HDDs. The noise level tolerance
of HDDs may vary among dierent models, designs, capacities and
manufacturers. The recommended acoustic noise level for an operating
environment is 90dB or less in order to ensure reliable operations when placing a
Hitachi Vantara storage system two meters from the source of the noise.