Chapter 2 – Electromagnetically compatible installation of drives and drive systems 
2-5 
Minimizing radiated interference 
 
The  frequency inverter of series WJ200 meet the  limits of EN61800-3, C1/C2/C3,  for radiated 
interference,  if  the  specified  line  filter  is  used  and  installation  is  performed  according  to  our 
instructions. 
The prerequisite is that all analog and digital control lines are laid shielded. 
With compact systems, if for example the frequency inverter is communicating with the steering 
unit, in the same control cabinet connected at the same PE-Potential, the screen should be put on, 
on both sides with PE. 
With branch systems, if for example the communicating steering unit is not in the same control 
cabinet and there is a distance between the systems, we recommend to put on the screen only on 
the side of the frequency inverter. If it is possible, direct in the cable entry section of the steering 
unit. This is very important, if there is a long distance between the system and you expect there can 
be different PE-Potential between the systems. 
You should allow the effective shield area of these lines to remain as large as possible; i.e., do not 
move  the  shield  further  away  than  absolutely  necessary.  The  distance  between  an  interference 
source and an interference sink (interference-threatened device) essentially determines the effects 
of the emitted interference on the interference sink. The interference field emitted by the frequency 
inverter  falls  sharply  with  increasing  distance.  Please  note  that  the  emitted  interference  field 
(frequency range 30 MHz - 1 GHz) of a drive (drive system) is measured at a distance of 10 m in 
accordance with EN61800-3. Every device placed closer than 10 m to a source of interference will 
thus be impacted by appreciably higher interference amplitudes. For this reason, you should use 
only interference-free devices and maintain a minimum distance of 0.25 m from the drive. Devices 
which react sensitively to interference from electric and magnetic fields should be kept at least a 
distance of 0.25 m from the following components: 
  Frequency inverter 
  EMC input/output filters 
  Input or output reactors/transformers 
  Motor cable (even if shielded) 
  External rheostat and its wiring (even if shielded) 
  AC/DC commutator motors, including any attached separate fans 
  DC intermediate circuit coupling/wiring (even if shielded) 
  Connected inductors like relays, contactors, solenoid valves, brakes (even if shielded) 
Very  frequently,  interference  is  coupled  in  through  installation  cables.  You  can  minimize this 
influence by laying interfering cables separately, a minimum of 0.25 m from cables susceptible to 
interference.  A  particularly  critical  point  is  laying  cables  parallel  over  larger  distances.  If two 
cables intersect, the interference is smallest if they intersect at an angle of 90°. Cables susceptible 
to  interference  should  therefore  only  intersect  motor  cables,  intermediate  circuit  cables,  or  the 
wiring of a rheostat at right angles and never be laid parallel to them over larger distances.