EasyManua.ls Logo

Hitachi WL200 Series

Hitachi WL200 Series
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 Setting
19
7.2.1 A001 (Frequency source)
You need to set A001 to 04 in the case of operation WJ200 / WL200 using the PROFINET
communication.
7.2.2 A002 (Run command source)
You need to set A002 to 04 in the case of operation WJ200 / WL200 using the PROFINET
communication.
7.2.3 A004 (Maximum frequency)
The range of frequency that you can monitor or set is from -100% to 100% in PROFIdrive. You need
to set base frequency.
7.2.4 A038 (Jog frequency)
WJ-PN supports Jog mode in Operation status of PROFIdrive. You need to set jog frequency.
7.2.5 A039 (Jog stop mode)
You need to set how the inverter stops. 00 is same as 03 (Free run stop), 01 is same as
04 (Controlled deceleration), 02 is same as 05 (DC braking to stop).
7.2.6 A093 (Deceleration time (2))
You need to set deceleration time when you use quick stop and C005 to 09 (2ch).
7.2.7 b031 (Software lock mode selection)
You need to set b031 to 10 (changeable mode during driving), if you rewrite the mutable
parameters of the WJ200 / WL200 during operation by the PROFINET communication. If you have not
already set to 10 (changeable mode during driving), it cannot be rewritten even after the rewrite of the
parameters.
7.2.8 C001 - C007 (Input [1-7] function)
You need to set C001 - C007 expect 06 (JG). If you set 06 (JG), Jog mode doesn’t work normally.
7.2.9 C005 (Input [5] function)
You need to set C005 to 09 (2CH), if you use the settings of the two-stage acceleration and
deceleration during the deceleration in the Quick stop of CiA402. WJ200 / WL200 normally
decelerates when you use quick stop of the two-stage acceleration and deceleration without the
above setting.
7.2.10 C006 (Input [6] function)
You need to set C006 to 83 (HLD), if you use the freeze ramp generator function that STW1 bit5 is
OFF. If you dont set C006 to 83 and STW1 bit5 is OFF, output frequency isn’t freeze.
7.2.11 C042 (Frequency arrival setting for acceleration)
When the output frequency is over the frequency that is set to C042 during acceleration, ZSW1
bit10 becomes ON. If you set C042 to 0, ZSW1 bit10 doesnt become ON.
7.2.12 C043 (Frequency arrival setting for deceleration)

Other manuals for Hitachi WL200 Series

Related product manuals