Chapter 8 PROFINET Specification
51
61003
Sub-Index
Item
Description
-
Name
StandardGatewayOfStation
Data type
STR (4 characters)
Access
R
Default setting
-
Detail
This area displays the default gateway address of this device.
61004
Sub-Index
Item
Description
-
Name
SubnetMaskOfStation
Data type
STR (4 characters)
Access
R
Default setting
-
Detail
This area displays the subnet mask of this device.
8.13.4 PROFIdrive area
Inverter parameters are allocated to objects 1000 to 1037 and 2000 to 2037. 1000 to 1037 are
2-byte parameters and 2000 to 2037 are 4-byte parameters.
Index and sub-index calculation method
Index: 1000 + (Inverter register number / 254), 2000 + (Inverter register number / 254)
Sub-Index: 1 + (Inverter register number % 254),
Where
(Inverter register number / 254) is the Integer part after the inverter register number is divided by
254.
(Inverter register number % 254) is the remainder after the inverter register number is divided by
254.
Please refer to Appendix object list for details.