Appendix PROFINET Object List
92
Index
Sub-
inde
x
Register
number
Size
[bite]
Functio
n
code
Name
R/W
Description and range
Resolutio
n
WJ200
only
1019
0x92
0x136B
02
(UINT)
b104
Free V/F
setting,
freq.3
R/W
0 to free V/F setting,
frequency 4 (b106)
1[Hz]
1019
0x93
0x136C
02
(UINT)
b105
Free V/F
setting,
voltage.3
R/W
0 to 8000
0.1[V]
1019
0x94
0x136D
02
(UINT)
b106
Free V/F
setting,
freq.4
R/W
0 to free V/F setting,
frequency 5 (b108)
1[Hz]
1019
0x95
0x136E
02
(UINT)
b107
Free V/F
setting,
voltage.4
R/W
0 to 8000
0.1[V]
1019
0x96
0x136F
02
(UINT)
b108
Free V/F
setting,
freq.5
R/W
0 to free V/F setting,
frequency 6 (b110)
1[Hz]
1019
0x97
0x1370
02
(UINT)
b109
Free V/F
setting,
voltage.5
R/W
0 to 8000
0.1[V]
1019
0x98
0x1371
02
(UINT)
b110
Free V/F
setting,
freq.6
R/W
0 to free V/F setting,
frequency 7 (b112)
1[Hz]
1019
0x99
0x1372
02
(UINT)
b111
Free V/F
setting,
voltage.6
R/W
0 to 8000
0.1[V]
1019
0x9A
0x1373
02
(UINT)
b112
Free V/F
setting,
freq.7
R/W
0 to 400
1[Hz]
1019
0x9B
0x1374
02
(UINT)
b113
Free V/F
setting,
voltage.7
R/W
0 to 8000
0.1[V]
1019
0xA2
0x137B
02
(UINT)
b120
Brake
control
enable
R/W
00: disabled
01: enabled
-
1019
0xA3
0x137C
02
(UINT)
b121
Brake Wait
Time for
Release
R/W
0 to 500
0.01[s]
1019
0xA4
0x137D
02
(UINT)
b122
Brake Wait
Time for
Acceleratio
n
R/W
0 to 500
0.01[s]
1019
0xA5
0x137E
02
(UINT)
b123
Brake Wait
Time for
Stopping
R/W
0 to 500
0.01[s]

Other manuals for Hitachi WL200 Series