HQ Series Quarter-turn Electric Actuator
Installation Operation& Maintenance Manual
Doc No. : HumG-HQ-21 Rev2 Page 5 / 26 Valve Automation Leader, HKC
3. General Information and Features
3.1. General information
HKC HQ-series electric actuators are designed for the operation of industrial valves; e.g. butterfly valves
and ball valves. The actuator torque outputs range from 40 Nm to 8,830 Nm (350 In-Lbs to 78,120 in-
Lbs). Currently 19 models are available. [In case of explosion proof or dust ignition proof type, the rated
current may be different due to the difference in the approved data, so please contact HKC. –--21 r0]
3.1.1. Standard technical data
HQ
(Model)
Max.
output
torque
Operating
time(sec)
50/60Hz
Max
bore
size
Rated current (A, tolerance ±10%), (50/60 Hz)
Duty
rate
No. of
handle
turn
Weight
DC
AC, 1 phase, 50/60 Hz AC, 3 phase, 50/60 Hz
kgf.m
90° Ømm
24
100 110 200 220 240 50Hz
380 440 460 S4(%)
n kg
HQ-004
4 12 / 12 11
0.5
0.2 / 0.2
0.1 / 0.1
0.2 / 0.2
0.1 / 0.1
- NA NA4 NA5 70 8 1
HQ-005
5 11 / 11 14
1 - 0.1 / 0.1
- 0.1 / 0.1
- - - - 70 10 3
HQ-006
6 14 / 12 14
1.7
0.5 / 0.5
0.4 / 0.4
0.3 / 0.3
0.2 / 0.2
0.2 NA NA NA 35 8 3
HQ-008
8 16 / 13 20
3.7
1.3 / 1.3
1.2 / 1.1
0.7 / 0.6
0.6 / 0.6
0.7 0.2 / 0.3
0.6 / 0.4
NA 70 10 7
HQ-010
10 20 / 17 20
4 1.3 / 1.3
1.2 / 1.1
0.7 / 0.7
0.7 / 0.6
0.7 0.2 / 0.3
0.6 / 0.4
NA 70 10 7
HQ-015
15 25 / 21 22
5.3
2.4 / 2.2
2.1 / 2.0
1.1 / 1.1
1.0 / 1.0
1 0.6 / 0.4
0.6 / 0.4
0.6 / 0.4
70 11 17
HQ-020
20 25 / 21 22
6.5
2.5 / 2.3
2.2 / 2.1
1.2 / 1.2
1.1 / 1.1
1.1 0.7 / 0.5
0.6 / 0.4
0.6 / 0.4
70 11 17
HQ-030
30 31 / 26 35
8.6
2.3 / 2.7
2.1 / 2.4
1.1 / 1.4
1.0 / 1.3
1.1 0.6 / 0.5
0.4 / 0.3
0.4 / 0.3
70 13.5
22
HQ-050
50 31 / 26 35
12.8
3.6 / 4.6
3.3 / 4.2
1.9 / 2.1
1.7 / 1.9
1.3 0.9 / 0.8
0.8 / 0.5
0.7 / 0.5
70 13.5
23
HQ-060
60 31 / 26 35
NA
3.8 / 4.9
3.4 / 4.4
2.1 / 2.3
1.9 / 2.0
1.3 1.0 / 0.9
1.4 / 0.9
1.3 / 0.9
70 13.5
23
HQ-080
80 37 / 31 45
NA
6.0 / 6.3
5.4 / 5.7
2.9 / 3.1
2.6 / 2.8
2.6 1.3 / 1.0
1.7 / 0.9
1.6 / 0.9
70 16.5
29
HQ-120
120
37 / 31 45
NA
7.2 / 7.6
6.5 / 6.9
3.1 / 3.3
2.8 / 3.0
2.9 1.5 / 1.1
1.8 / 1.0
1.7 / 0.9
70 16.5
29
HQ-200
200
37 / 31
(1)
65
NA
6.0 / 6.3
5.4 / 5.7
3.4 / 3.3
3.1 /3.0
3.1 1.4 / 1.0
1.7 / 1.0
1.6 / 0.9
50 49.5
75
HQ-270
270
56 / 47
(1)
65
NA
7.0 / 7.4
6.3 / 6.7
3.5 / 3.4
3.2 / 3.1
3.2 1.5 / 1.1
1.8 / 1.0
1.7 / 0.9
50 49.5
75
HQ-300
300
112 / 93
65
NA
7.2 / 7.6
6.5 / 6.9
3.1 / 3.3
2.8 / 3.0
2.9 1.5 / 1.1
1.8 / 1.0
1.7 / 0.9
50 49.5
75
HQ-350
350
39 / 33 75
NA
24.9 / 19.2
22.6 / 17.4
12.4 / 9.5
11.2 / 8.7
11.2 4.2 / 3.0
3.8 / 2.6
3.6 / 2.5
40 42 75
HQ-400
400
58 / 49 75
NA
24.9 / 19.2
22.6 / 17.4
12.4 / 9.6
11.2 / 8.7
11.3 4.2 / 3.0
3.8 / 2.6
3.6 / 2.5
40 42 75
HQ-600
600
78 / 66 110
NA
16.3 / 11.6
14.8 / 10.5
9.9 / 7.0
9.0 / 6.3
- 3.6 / 3.3
2.1 / 1.8
2.0 / 1.7
40 84 215
HQ-900
900
117 / 99
110
NA
16.3 / 11.6
14.8 / 10.5
9.9 / 7.0
9.0 / 6.3
- 3.6 / 3.3
2.1 / 1.8
2.0 / 1.7
40 84 215
Note :Technical data of above may be changed without pre-notice.
[(1) Operating time of 110V ac 1ph is applied 112/93.
(2) Above data shall be applied separately for Explosion proof type actuators in accordance
with relevant approval certificate --- 19 Rev1]
[(3) Delete HQ-800, 1000, 1100 models --- 20 r0]
3.1.2. Hand Wheel and Declutching
HQ-series actuators are provided with a declutchable manual override
system.
In order to manually operate the actuator, pull the manual override
engagement level towards the hand-wheel until it remains in position.
Turn the hand-wheel until the valve reaches the required position.
Turn clockwise to close and counter-clockwise to open.
3.1.3. Additional standard technical data
Enclosure Rat
ing
Ingress protection
IP67, NEMA 4
,4X
& 6
Enclosure
High grade aluminium alloy,
Anti
-
corrosion coated
Motor
Squirrel caged induction motor
Limit Switches
2 x open/close SPDT, 250 V
ac
16A rating
Auxiliary Limit Switches
2 x open/close SPDT, 250 V
ac
16A rating
[
(except HQ
-
008
/010
)
-
1
7
R
0
]
Torque
Switches
Open/close SPDT, 250V
ac
1
6
A Rating
[
(except HQ
-
008
/010
)
-
1
7
R
0
]
Stall Protection
Built
-
i
n thermal protection
Travel Angle
90 degree +/
-
10%
Indicator
Continuous position indicator
Self
-
Locking
By means of worm gear
Mechanical Travel Stops
2 x
external adjustable mechanical travel stops
Cable
Entries
[
2xNPT 3/4”
,
2xM25
for Ex db, additionally M20, M25 and NPT3/4
with
M
30
adaptor
for E
x tb.
(
by u
ser selection)
----
17 Rev0
]
Lubrication
Grease moly EP which will be almost permanently lubricated
. However,
periodical preventive maintenance will extend the operating life
Ambient Temperature
-
20 ℃~ + 60 ℃(except on CPT & PCU board )
External Coating
Dry powder polyester
coating, [max thickness 2mm for Ex tb application
---- 17r1]

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HKC HQ Series and is the answer not in the manual?

HKC HQ Series Specifications

General IconGeneral
BrandHKC
ModelHQ Series
CategoryController
LanguageEnglish

Related product manuals