Troubleshooting
In case of an error in the radio communication or the transmission of data
between the electronic box and the RCL controller, the system comes up with
the following error messages:
The ERROR diode on the electronic box flashes
The RUN and FUNC diodes on the RCL indicator panel are flashing
It will now be possible to troubleshoot by pushing and holding down the red
press button on the RCL indicator panel.
Now a diode indicates where to find the error in the system.
Flashing diode Type of error Remedy
85% diode The IRC-system has not
been started up
Re-start the IRC-System
90% diode Start up error in the Can-bus
communication
Re-start the IRC-System
100% diode The RCL controller has been
set for emergency operation
Change back into remote
control mode. Please see
chapter on Emergency
Operation.
80%, 85% diodes The stop button on the
remote control box is
activated (pushed in)
Pull out the stop button (turn
it to the right)
80%, 90% diodes Error at the cable connection
for the dump valve input in
the RCL
Please contact an authorised
HMF service point.
If problems continue, contact immediately an authorised HMF service point.