Installation Guide 2
© 2005-2009 HMS Industrial Networks.
Installation Items Checklist
• Anybus-X Ethernet to DeviceNet Gateway (part number AB7607).
Anybus-X Ethernet to DeviceNet Gateway User Manual downloadable from
http://www.anybus.com and go to the support section
• Power cable for connection to supplied 2 position connector.
• DeviceNet cable for connection to supplied 5 position connector.
• Ethernet cable for connection to RJ-45 connector.
• DeviceNet configuration tool such as RSNetworx for DeviceNet or NetTool-
DN.
• EDS file, AB7607.eds, downloadable fromhttp://www.anybus.com and go to the
support section.
Installation and operation requirements
Power, input and output (I/O) wiring must be in
accordance with Class 1, Division 2 wiring methods
– article 501-4 (b) of the National Electric code,
NFPA 70 and in accordance with local codes.
Warning – Explosion Hazard – Substitution of
components may impair suitability for class 1,
Division 2.
Warning – Explosion Hazard – When in hazardous
locations turn off power before replacing or wiring
modules.
Warning – Explosion Hazard – Do not disconnect
equipment unless power has been switched off or the
area is known to be nonhazardous.
Terminal tightening torque must be between 5 – 7
lbs-in (0,5-0,8 Nm).
For use in Class 2 circuits only.
Suitable for Surrounding temperature of 65 C max.
Use 60/75 C copper wire only.