E-MON CLASS 3400 METER
47 62-0398—02
11.2 Pulse Type and Value
The pulse outputs provided by the E-Mon Class 3400 Meter are watt-hours and
var-hours. Output 1 is the watt-hour pulse and Output 2 is the var-hour pulse.
The pulse value is dependent on the amperage size of the meter. See the chart
below for the values also true for expansion board pulse output.
NOTE: The standard pulse option is not functional when used with the
expanded feature package.
Fig. 24. E-Mon Class 3400 Meter Standard Watt-hour Pulse Output.
Meter Amps Watt-hours / pulse Var-hours / pulse
100 1.95313 1.95313
200 3.90625 3.90625
400 7.8125 7.8125
800 15.625 15.625
1600 31.25 31.25
3200 62.5 62.5
M34374
SELECTION PINS 1 AND
2 FOR WATT-HOURS VIA
3 POSITION JUMPER J43
THE WATT-HOUR OUTPUT
IS THE 2 POSITION TERMINAL
BLOCK HERE
62-0398-02.fm Page 47 Tuesday, May 8, 2018 10:22 AM