E-MON CLASS 3400 METER
51 62-0398—02
41067 2 Float Voltage, line to line, phase B-C Volts-L R
41069 2 Float Voltage, line to line, phase C-A Volts-L R
41071 2 Float Phase angle, phase A Degree R
41073 2 Float Phase angle, phase B Degree R
41075 2 Float Phase angle, phase C Degree R
41083
2
2 Float External Input 1 Pulse R/W
41085
2
2 Float External Input 2 Pulse R/W
44001
3
6Custo
m
Interval Day Block R/W
44007
4
1 per
interval
Integer Interval Data Pulse R
45501
5
2 per day Custo
m
Interval Data Headers R
46025
6
8Custo
m
RTC Date/Time R/W
46049
7
8Custo
m
EZ7 ID, ModBus ID, Serial
Number
R/W
46057 8 Custo
m
Recorder Info., Demand
Interval
R/W
46513 8 Custo
m
Flags L1: Power Failure,
Battery
R
46521 8 Custo
m
Flags L2: Power Failure Date R
1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8
points with data set to 0000 0000 0000 0000 0000 0000 0000 0000. Remove
Jumper J6 after changes have been made.
2. External inputs are standard on Class 5000 meters and optional on Class 3400
meters (Part of Expanded Feature Package).
To clear external inputs, set multiple points at 41083 or 41085 for 2 points with
data set to 0000 0000. Jumper J6 must be closed. Remove Jumper J6 after
changes have been made.
3. To set the interval data day block, set multiple points at 44001 for 6 points with
data set to 0C0I 0000 MMDD YYYY 0000 0000.
0C = Channel, 0I = Interval (0F = 15 minute intervals, 05 = 5 minute intervals)
4. Each register represents a 15 or 5 minute kWh pulse value based on the
interval day block. 96 registers max with 15 minute intervals. 288 registers max
with 5 minute intervals. The first interval data register 44007 represents the
pulse count for the first 15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day
represents 2 registers. Format: MMDD YYYY.
6. To set the date and time, set multiple points at 46025 for 4 points with data set
to HHMM SSDW MMDD YYYY (DW=day of week)
7. To change the ModBus ID, set single point at 46050 with data set to new
ModBus ID (e.g. 1 to 247). Jumper J6 must be closed.
ModBus Customer Point Map: CL3400
Address Registers Format Description Units
CL
3400
62-0398-02.fm Page 51 Tuesday, May 8, 2018 10:22 AM