RM7888A 7800 SERIES RELAY MODULE
5 32-00214—01
Table 3. Composition of Each Combination.
ABCDF
4.5A ignition 50 VA Pilot Duty plus
4.5A ignition
180 VA Ignition plus
Motor Valves with:
660 VA inrush,
360 VA open,
250 VA hold.
2A Pilot Duty 65 VA Pilot Duty plus
motor valves with:
3850 VA inrush,
700 VA open,
250 VA hold.
Table 4. Flame Detection Systems (FIGS. 2–8).
Plug-In Flame Signal Amplifiers Applicable Flame Detectors
Type Color
Self-
Checking Model
Flame
Failure
Response
Time (sec)
a
Fuel Type Models
Rectification Green No
R7847A
e
0.8 or 3 Gas Rectifying
Flame Rod
Holders
h
C7004,
C7007,
C7011
Complete
Assemblies:
C7008,
C7009, Q179
No
R7847A
e
3 Gas, oil, coal Ultraviolet
(Purple
Peeper)
C7012A,C
Dynamic
Amplicheck
®
R7847B
c,e
0.8 or 3 Gas Rectifying
Flame Rod
Holders
h
C7004,
C7007,
C7011,
Complete
Assemblies:
C7008,
C7009, Q179
Dynamic
Amplicheck
R7847B
c,e
3 Gas, oil, coal Ultraviolet
(Purple
Peeper)
C7012A, C
Dynamic
Self-check
R7847C
g
3 Gas, oil, coal Ultraviolet
(Purple
Peeper)
C7012E, F
Infrared Red/White No R7852A 3 Gas, oil, coal Infrared C7915
Dynamic
Amplicheck
R7852B 3 Gas, oil, coal Infrared C7915
Ultraviolet Purple No R7849A 0.8 or 3 Gas, oil Ultraviolet
(Minipeeper)
C7027,
C7035,
C7044
d
Dynamic
Amplicheck
R7849B
d
0.8 or 3 Gas, oil Ultraviolet
(Minipeeper)
C7027,
C7035,
C7044
d
Dynamic
Self-Check
R7861A
b
0.8 or 3 Gas, oil, coal Ultraviolet C7061
Blue Dynamic
Self-Check
R7886 3 Gas, oil, coal Ultraviolet
(Adjustable
sensitivity)
C7076
Optical White Dynamic
Amplicheck
R7851B 0.8 or 3 Gas, oil, coal Optical (UV,
Visible Light)
C7927,
C7962
Dynamic
Self-Check
R7851C
b
3 Gas, oil, coal Optical (UV
only)
C7961