Internet Communication Module 7845i-GSM Installation and Setup Guide
3-16
PROMPTS ZONE
TRIG.
4204/
2-4204
ENTRY OPTIONS DESCRIPTION
54
Enable Zn6 Y/N
(N)_
4204
only
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 60: "Enable Zn7."
55
Zn6 Trigger Type
(V+)_
4204
only
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
56
Invert Zn6 Y/N
(N)_
4204
only
[Y], [N] Inverts the alarm and normal states of the zone
6 trigger; otherwise uses normal input signal.
57
Restore Zn6 Y/N
(Y)_
[Y], [N] Enables restore reporting for zone 6.
58
Delay Zn6 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 6.
59
Rpt Zn6 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 6 ONLY if the
conditional zone (zone 7 in zone trigger mode;
zone 4 in 4204 mode; zone 8 in 2-4204 mode) is
triggered (armed).
If [N], always reports alarms on zone 6.
60
Enable Zn7 Y/N
(N)_
4204
only
[Y], [N] Enables alarm reporting for zone 7.
If [N], skip to Prompt 68: "Use DHCP."
61
Zn7 Trigger Type
(V+)_
4204
only
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
62
Invert Zn7 Y/N
(N)_
4204
only
[Y], [N] Inverts the alarm and normal states of the zone
7 trigger; otherwise uses normal input signal.
63
Restore Zn7 Y/N
(Y)_
[Y], [N] Enables restore reporting for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.
64
Delay Zn7 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.
65
Rpt Zn7 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 7 ONLY if the
conditional zone (zone 4 in 4204 mode; zone 8 in
2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 7.
2-4204 mode: If any zone is programmed to
"Report Only if Armed," or if tamper is enabled,
skip to Prompt 68: "Use DHCP."
66
Restore Zn8 Y/N
(Y)_
2-
4204
only
[Y], [N] Enables restore reporting for zone 8.
67
Delay Zn8 (secs)
(00)_
2-
4204
only
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 8.
68
Use DHCP Y/N
(Y)_
[Y], [N] Dynamically allocates the IP addresses
(recommended); then skip to "Review".
If [N], uses fixed IP addresses.

Table of Contents