40
APT4000PH
Configuration
Output 2
Temperature unit and probe. Output current.
Select °C/°F
Select temperature probe
Select 0-20 / 4-20 mA
Enter current beginning
Enter current end
Set output filter
22 mA for temp error
Hold mode
End:
Press CONF, then ENTER
Code
Display
Menu group
Select menu item
Output 2
o2.
41
°C
(°F)
Code
Display
Action
Choices
o2.
Specify temperature unit
Select with key
Proceed with ENTER
Select temperature probe
Select with key
Proceed with ENTER
NTC8.55
(NTC30,
PT100,
PT1000)
4–20 mA
(0–20 mA)
Set output current range
Select with key
Proceed with ENTER
Current beginning:
Enter lower end of scale.
Select with key, edit number with
key, proceed with ENTER
000.0 °C
(XXX.X)
Current end:
Enter upper end of scale.
Select with key, edit number with
key, proceed with ENTER
100.0 °C
(XXX.X)
Output current
Process temperature
204
100
0
Process temperature: Current beginning and current end
Process temperature
204
70
50
[mA]
Example 1: Range 0 to 100 °C Example 2: Range 50 to 70 °C.
Advantage: Higher resolution in
range of interest
[°C]
[°C]
[mA]