BCU 370 · Edition 01.19 25
Function
3.2.4 Start-up without pre-purge,
butterfly valve waits in the Closed
position
Parameter 18 = 0, parameter 28 = 1
If a fault from the preceding operat-
ing cycle is still being signalled after
switching on, it will be necessary
to reset this first. Once the start-
up signal (ϑ) has been applied, the
switch-on delay t
E
starts to elapse.
Afterwards, the buttery valve
moves from the Closed to the Open
position and then to the Ignition po-
sition. During the fan run-up time
t
GV
which follows, the fan starts
with the buttery valve being set to
Ignition position.
After the waiting time t
W
, the BCU
activates pre-ignition t
VZ
and then
opens valves V1 and V2 for the
pilot burner. The ignition time t
Z
is
constant. After the flame proving
period for the pilot burner t
FS1
, valve
V3 opens to ignite the main burner.
H0
04
05
06
07
08
00
00
H0
01
A1
A0
A2
03
H8
08
P9
02
Switch on BCU 370
Start-up with ϑ signal
In the event of fault signal: reset
Fan run up time t
GV
(P20)
Switch-on delay time t
E
running (P22)
Start-up position/standby
Start-up position/standby
Controlled shut-down
via ϑ signal
Flame proving period t
FS1
running for burner/pilot burner (P13)
Safety time t
SA1
running for
burner/pilot burner (P12),
V1 and V2 open
Butterfly valve moves to Open position
Butterfly valve moves to Closed position
Flame proving period t
FS2
running for main burner (P15)
Safety time t
SA2
running for main burner (P14),
V3 opens
Butterfly valve moves to Ignition position
Pre-ignition time t
VZ
running (P21d
Ignition activated
Controller enabler signal delay time t
RF
(P29)
Controller enable signal
Post-purge time t
PN
running (P19)
If parameter P27 = 0:
V2 is switched off
Waiting time t
W