BCU 370 · Edition 01.19 23
Function
3.2.3 Quick start, butterfly valve
waits in the Closed position
Parameter 06 = 0, parameter 28 = 1
Pre-purge will also be omitted for
this type of quick start. To prevent
cold air from entering the combus-
tion chamber while the BCU is in
start-up position/standby, the but-
terfly valve waits in the Closed posi-
tion.
The BCU 370 only carries out a
quick start if the last shut-down
was a controlled shut-down. No
more than 24 hours may have
elapsed and the BCU must have
been switched on.
After the switch-on delay time t
E
,
the buttery valve moves to the Ig-
nition position. The Ignition position
is always approached from the top.
Therefore, the buttery valve moves
to the Open position first.
H0
05
06
07
08
00
00
H0
01
A1
A0
A2
H8
08
P9
04
03
02
Start-up with ϑ signal
Fan run up time t
GV
(P20)
Waiting time t
W
Switch-on delay time t
E
running (P22)
Start-up position/standby
Start-up position/standby
Controlled shut-down
via ϑ signal
Flame proving period t
FS1
running for burner/pilot burner (P13)
Butterfly valve moves to Open position
Butterfly valve moves to Closed position
Flame proving period t
FS2
running for main burner (P15)
Safety time t
SA2
running for main burner (P14),
V3 opens
Butterfly valve moves to Ignition position
Controller enabler signal delay time t
RF
(P29)
Controller enable signal
Post-purge time t
PN
running (P19)
If parameter P27 = 0:
V2 is switched off
Safety time t
SA1
running
for burner/pilot burner (P12),
V1 and V2 open
Pre-ignition time t
VZ
running (P21)
Ignition activated