EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 
EN1Z-1039GE51 R1218  2 
SAFETY INFORMATION 
General Safety Information 
►  When performing any work, all instructions given by the 
manufacturer and in particular the safety instructions 
provided in these Installation and Commissioning 
Instructions are to be observed. Make sure that the local 
standards and regulations are observed at all times. 
►  The EAGLEHAWK NX System (including the 
EAGLEHAWK NX controller, Panel Bus I/O modules, 
manual disconnect modules, and auxiliary terminal 
packages) may be installed and mounted only by 
authorized and trained personnel. 
►  If the controller housing is damaged or missing, 
immediately disconnect it from any power. 
►  If the device is broken or defective, do not attempt to repair 
it yourself; rather, return it to the manufacturer. 
►  It is recommended that devices be kept at room tem-
perature for at least 24 hours before applying power. This 
is to allow any condensation resulting from low shipping / 
storage temperatures to evaporate. 
►  The EAGLEHAWK NX System must be installed in such a 
manner (e.g., in a lockable cabinet) as to ensure that 
uncertified persons have no access to the terminals. 
►  In the case of vertical mounting on DIN rails, the 
EAGLEHAWK NX controller should be secured in place 
using a commercially-available stopper. 
►  If the EAGLEHAWK NX System is modified in any way, 
except by the manufacturer, all warranties concerning 
operation and safety are invalidated. 
►  Rules regarding electrostatic discharge should be followed. 
►  Use only accessory equipment which comes from or has 
been approved by Honeywell. 
 
Information as per EN 60730 
Purpose 
The purpose of the device is: OPERATING CONTROL. The 
EAGLEHAWK NX controller is a multifunctional non-safety 
control device intended for HVAC in home (residential, 
commercial, and light-industrial) environments. 
 
Construction 
The EAGLEHAWK NX controller is an independently mounted 
electronic control unit with fixed wiring. 
 
Mounting Method 
The EAGLEHAWK NX controller is suitable for mounting as 
follows: 
►  in cabinets; 
►  in fuse boxes conforming with standard DIN43880, and 
having a slot height of max. 45 mm; 
►  in cabinet front doors (using accessory MVC-80-AC2); 
►  on walls (using accessory MVC-80-AC1). 
 
Table 1. Information as per EN 60730 
Shock protection 
Class II 
Pollution degree 
2 
Installation 
Class 3 
Rated impulse voltage 
330 V for SELV, 2500 V for relay 
outputs 
Automatic action 
Type 1.C (micro-interruption for 
the relay outputs) 
Software class 
Class A 
Ball-pressure test 
temperature 
housing parts >75 °C 
terminals >125 °C 
 
WEEE Directive 
WEEE: Waste Electrical and Electronic 
Equipment Directive 
 
  At the end of the product life, dispose 
of the packaging and product in an 
appropriate recycling center. 
  Do not dispose of the device with the 
usual domestic refuse. 
  Do not burn the device. 
 
Standards, Approvals, etc. 
Degree of Protection:  IP20 (mounted on walls, with two 
accessory MVC-80-AC1 covers) 
  IP30 (mounted in cabinet doors, with 
accessory MVC-80-AC2) 
Device meets EN 60730-1, EN 60730-2-9, UL60730, and 
UL916. 
Refer to Code of Practice standards IEC 61000-5-1 and -2 
for guidance. 
The device complies with Ethernet Protocol versions IEEEC 
802.3. 
The device supports BACnet IP and BACnet MS/TP 
communications as per ANSI / ASHRAE 135-2012. 
 
3RD-PARTY SOFTWARE LICENSES 
This product contains software provided by third parties. See 
also EAGLEHAWK NX Controller – Third-Party Software 
Licenses (Product Literature No.: EN2Z-1041GE51).