EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 
EN1Z-1039GE51 R1218  46 
M-BUS CONNECTION 
The EAGLEHAWK NX controller supports M-Bus Master 
functionality via its onboard RS232 / RJ45 socket. 
It uses standard PW3/PW20/PW60 converters to connect to 
the M-Bus devices. 
 
M-Bus Considerations 
Max. no. of M-Bus devices per EAGLEHAWK NX: 60. 
 
Bus Length 
•  Max. M-Bus length: 350 meters from PW3 / PW20 / 
PW60, at communication rates of 9.6 kbps or slower with 
shielded, twisted pair cable: J-Y-(St)-Y 2 x 2 x 0,8. 
•  The M-Bus can be extended to 1,000 meters, depending 
upon the communication rate, and provided that the 
following electrical limitations are observed: 
˗  Bus voltage must at no point fall below 12 VDC 
˗  Maximum cable capacitance of 180 nF 
For bus length extension, M-Bus repeaters can be used, but 
have not been tested by Honeywell. Hence, it is the 
responsibility of the installing / commissioning personnel to 
ensure proper functioning. 
 
Wiring Topology 
M-Bus meters are connected to the bus cable in parallel. 
 
EAGLEHAWK
SLAVE 1 SLAVE 2 SLAVE 3
PW
CONVERTER
 
Fig. 51. Allowed M-Bus wiring topology 
 
Cabling EAGLEHAWK NX to PW3/PW20/PW60 
•  Use the XW586 cable between the RS232 / RJ45 socket 
of the EAGLEHAWK NX and the PW adapters. 
•  The XW586 cable has a length of 1.8 m, and the pin-out 
listed in Table 25. 
•  In case a third-party cable is used instead of the XW586 
cable, the third-party cable must have a max. length of 
15 meters and a max. cable capacitance of 2,500 pF. 
Table 24. EAGLEHAWK NX RS232 / RJ45 socket 
specifications 
RJ45 plug, 
pin no. 
RS232 function 
1   
2  RxD  
3  TxD 
4   
5  GND 
6   
7   
8   
 
876
5
4
3
21
 
Fig. 52. EAGLEHAWK NX RS232 / RJ45 socket 
 
Table 25. RS232-to-PW cable specifications 
RJ45 plug, 
pin no. 
RS232 function 
9-Pin sub-D 
connector pin no.
1  DCD  1 
2  RxD   2 
3  TxD  3 
4  DTR  4 
5  GND  5 
6  DSR  6 
7  RTS  7 
8  CTS  8 
--  Not used  9 
 
1
 
5
 
4
 
3
 
2
 
9
 
8
 
7
 
6
 
12
3678
4
5
RS232 plug
sub-D male
SHIELD
D
C
D
D
S
R
R
x
D
R
T
S
T
x
D
C
T
S
D
T
R
G
N
D
XW586 
RJ45 plug with clip at front 
+5V
 
Fig. 53. XW586 power / communication cable details 
 
Cabling PW3/PW20/PW60 to M-Bus 
•  Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8. 
•  Shielding is especially recommended when the M-Bus 
cable is installed in areas with expected or actual electro-
magnetic noise. Avoiding such areas is to be preferred. 
•  Connect the shield to a noise-free earth ground – only 
once per M-Bus connection. 
•  Power the EAGLEHAWK NX controller and the PW M-Bus 
Adapter with separate transformers – see WARNING 
below. 
NOTE:  If, alternatively, only a single transformer is available, 
when connecting a laptop, PC, web browser, CL-
Touch, or 3
rd
-party touch panel to the USB 2.0 
Device Interface on the front of the EAGLEHAWK 
NX controller, use an optical isolator for the USB 
connection or substitute an M-Bus Mikro-Master 
USB (Relay GmbH, D-33106 Paderborn) for the PW 
M-Bus Adapter.