EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1039GE51 R1218 6
Bus and Port Connections
Overview
WARNING
Risk of electric shock or equipment damage!
► Do not touch any live parts in the cabinet!
► Disconnect the power supply before making connections
to or removing connections from terminals of the
EAGLEHAWK NX controller or Panel Bus I/O modules.
► Do not reconnect the power supply until you have
completed installation.
► Due to the risk of short-circuiting (see Fig. 23), it is
strongly recommended that the EAGLEHAWK NX con-
troller be supplied with power from a dedicated trans-
former. However, if the EAGLEHAWK NX controller is to
be supplied by the same transformer powering other con-
trollers or devices (e.g., the PW M-Bus Adapter), care
must be taken to ensure that correct polarity is observed.
► Observe the rules regarding electrostatic discharge.
24V-0
24V~
1
7 8
2
9
DO1
DO2
DO3
IN
IN4
DO4
DO5
IN5
IN6
DO6
DO7
IN7
IN8
DO8
GND
AO1
AO2
AO3
5 6 7 8 9 10 1112131415161718 1920 2122
AO4
23
24 25 26 27 28 29 30 31 32
5
6
GND1
485-1+
485-1-
n.a.
n.a.
GND2
485-2+
485-2-
n.a.
1 2 3 4
RS232
RS485-1
END
BIAS
MID
BI1
BI2
BI3
BI4
GND
UI1
UI2
UI3
UI4
UI5
UI6
UI7
33 34 35 36 37 38 39 40 41 42 43 44 45 46
UI8
47
UI9
UI10
21
Fig. 2. Top view (with HMI and full complement of
onboard I/Os)
1 2
END
BIAS
MID
4
3
Fig. 3. Side view
Legend
1 RS232 / RJ45 socket (for connection of M-Bus and
other RS232-based protocols; factory debugging)
2 Three-position slide switch (for setting bias and
termination resistance of RS485-1)
3 Two Ethernet / RJ45 sockets (for BACnet IP com-
munication); 10/100 Mbit/s; 1 "link" LED + 1 "activity"
LED
4 USB 2.0 Host Interface (for connection of IF-LON2);
max. 200 mA, high speed
5 RS485-1* (isolated; for BACnet MS/TP, Panel Bus,
Modbus RTU communication, etc.)
6 RS485-2* (non-isolated; for BACnet MS/TP, Panel
Bus, Modbus RTU communication, etc.)
7 LEDs
8 USB 2.0 Device Interface (for connection to COACH
NX web browsers, and 3
rd
-party touch panels)
9 HMI (or RJ45 socket for connection of portable HMI)
*Modbus RTU Master/Slave communication is possible on the
two RS485 interfaces.
WARNING
Risk of electric shock or equipment damage!
► It is prohibited to connect any of the RJ45 sockets of the
EAGLEHAWK NX controller to a so-called PoE-enabled
device ("Power over Ethernet").