EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
49 EN1Z-1039GE51 R1218
TROUBLESHOOTING
EAGLEHAWK NX Controller Troubleshooting
The following LEDs of the EAGLEHAWK NX controller can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
L1 and L2 LEDs (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of EAGLEHAWK NX
Table 28. EAGLEHAWK NX controller power LED
case power LED
meaning remedy
1
ON Normal operation. No action necessary.
2
OFF
Power supply not OK.
Check power supply voltage.
Check wiring.
If problem persists, replace hardware.
Status LED (red) of EAGLEHAWK NX
Table 29. EAGLEHAWK NX controller status LED
case status LED
!
meaning remedy
1
OFF after
power-up
Normal operation. No action necessary.
2
ON con-
tinuously after
power-up
Indicates an active alarm; is controlled by
Niagara Alarm System; is configurable.
Try powering down and then powering up the
EAGLEHAWK NX controller.
If problem persists, replace hardware.
L1 LED
Table 30. EAGLEHAWK NX controller bus L1 LED
case bus LED
L1
meaning remedy
1
ON con-
tinuously after
power-up
Normal operation; Daemon starting.
No action necessary.
2
Flashes
constantly
Station starting; if L2 is also flashing, then
the station has started.
No action necessary.
3
OFF
Severe software problems.
Contact TAC.