EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1039GE51 R1218 32
PANEL BUS CONNECTION
The EAGLEHAWK NX controller features two RS485 interfaces to which Panel Bus modules can be connected: RS485-1
(consisting of push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-
2]).
NOTE: GND-2 is internally connected with 24V-0 (terminal 1)
Overview of Panel Bus I/O Modules
XS821-22
XSU821-22
X
S823
XSU823
S824-25
X
SU824-25
EAGLEHAWK NX
PANEL BUSPANEL BUS PANEL BUS PANEL BUS
PANEL BUS I/O
ELECTRONIC
MODULES
pluggable
ANALOG OUTPUT
pluggable
ANALOG INPUT
pluggable
BINARY INPUT
pluggable
FLOATING
OUTPUT
CLIOP821A
CLIOPR822A
CLIOP822A CLIOP823A
pluggable
RELAY OUTPUT
CLIOPR824A CLIOPR825A
CLIOP824A
MIXED I/Os
(with integrated electronic module)
123456789101112
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND
Analog Out puts
AI2 AI3 AI4
14 15 16
AI1
17 18 19 20
13
Analog I nputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1NO2NO3NO4NO5NO6
CO1CO2CO3CO4CO5CO6
35
29 30 31 32 33 34
36 37 38 39 40
123456
Install. Instr.
MU1B-0473GE51
!
AI5 AI 6 AI 7 AI8
Honeywell
12
3
4
5678910
11 1 2
B1 B2 B3 B4
B5
B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND
Analog Out puts
AI2 AI3 AI4
14 15 16
AI1
17 18 19 20
13
Analog I nputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1NO2NO3NO4NO5NO6
CO1CO2CO3CO4CO5CO6
35
29 30 31 32 33 34
36 37 38 39 40
12
3
4
56
Install. Instr.
MU1B-0473GE51
!
AI5 AI 6 AI 7 AI8
Honeywell
CLIOP830A
CLIOP830A
CLIOP831A
CLIOP831A
Fig. 33. Overview of Panel Bus I/O Modules
Panel Bus Considerations
RS485-1 (isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 1200 meters (9.6 – 78.8 kbps) or 800 meters (115.2 kbps) (see also section "RS485 Standard" on pg. 10).
Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLEHAWK NX must be positioned at
one end of the Panel Bus, and an end termination (120 Ω) at the other end. Further, the three-position slide switch
(see Fig. 13 on pg. 9) must be set to "END."
RS485-2 (non-isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 1200 meters (9.6 – 78.8 kbps) or 800 meters (115.2 kbps) (see also section "RS485 Standard" on pg. 10).
Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLEHAWK NX controller must be
positioned at one end of the Panel Bus, and an end termination (120 Ω) at the other end.
- Must not extend beyond a single building or building floor
Max. no. of Panel Bus I/O modules per RS485 interface
- Max. no. of Panel Bus I/O modules of a given model: 16
- Total max. no. of Panel Bus I/O modules: 64
Max. no. of Panel Bus I/O modules per EAGLEHAWK NX
- Max. no. of Panel Bus I/O modules of a given model: 32
- Total max. no. of Panel Bus I/O modules: 128
Max. no. of hardware I/O points per EAGLEHAWK NX: 1000 (given a polling rate of 2 seconds; see also section
"Controller Performance" on pg. 48)
Refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information about
connection, current requirements, power supply, overvoltage protection, cable specifications, fusing, effects of manual overrides,
etc. of Panel Bus I/O modules and field devices connected to them.