EasyManua.ls Logo

Honeywell CENTRA LINE EAGLEHAWK - Rin-Apu24; Lightning Protection

Honeywell CENTRA LINE EAGLEHAWK
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1005GE51 R0216 12
24 V~
24 V~0
LINE
L
N
EAGLEHAWK #1 EAGLEHAWK #2
CPU 2
NOISE-FREE EARTH GROUND
(ONLY ONE PER SYSTEM)
N, L
EARTH GROUND
USB 2.0
Device Interface
!
REVERSED
POLARITY!
SHORT-CIRCUITING!
PC 1 PC 2
2 21 1
24V~ 24V~24V~0 24V~0
Fig. 20. Incorrect polarity SHORT-CIRCUITING!
Transformer Data
In Europe, if the EAGLEHAWK is powered by transformers,
then such transformers must be safety isolating transformers
conforming to IEC61558-2-6. In the U.S. and Canada, if the
EAGLEHAWK is powered by transformers, then such
transformers must be NEC Class-2 transformers.
Table 9. 1450 series transformers data
part #
1450 7287
primary side secondary side
-001 120 Vac 24 Vac, 50 VA
-002 120 Vac
2 x 24 Vac, 40 VA, 100 VA from
separate transformer
-003 120 Vac 24 Vac, 100 VA, 24 Vdc, 600 mA
-004 240/220 Vac 24 Vac, 50 VA
-005 240/220 Vac
2 x 24 Vac, 40 VA, 100 VA from
separate transformer
-006 240/220 Vac 24 Vac, 100 VA, 24 Vdc, 600 mA
Table 10. Overview of CRT Series AC/DC current
transformer primary side
max. AC
current
max. DC
current
CRT 2 230 Vac 2 A 500 mA
CRT 6 230 Vac 6 A 1300 mA
CRT 12 230 Vac 12 A 2500 mA
PRIMARY SIDE
EAGLEHAWK
1
2
24 VAC
230 VAC
120 VAC
24 V0
NOT
RECOMMENDED
Fig. 21. Connection of EAGLEHAWK controller
RIN-APU24
The RIN-APU24 Uninterruptable Power Supply can be
directly wired to an EAGLEHAWK controller.
See RIN-APU24 Uninterruptable Power Supply – Mounting
Instructions (EN0B-0382GE51) for a detailed wiring diagram.
Powering Panel Bus I/O Modules and Field Devices
The EAGLEHAWK, Panel Bus I/O modules, and field devices
can be powered by either separate transformers (see Fig. 22,
and Fig. 23) or by the same transformer.
NOTE: Use a min. distance of 10 cm between power cables
and 0…10 V / sensor cables in order to prevent
signal disturbances on the 0…10 V / sensor cables.
See also section “Cable Specifications” on page 18.
Powering Field Devices and Panel Bus I/O Module via Separate
Transformers
24 V actuator connected to, e.g., an analog output module
Field device located 100 … 400 m from the analog output
module
max. 400 m
CLIOP822A
73
74
1...8
GND
Y
24 VAC
11...18
24 V0
230 VAC
24 VAC
F2
Y (0...10 Vdc)
24 V0
230 VAC
24 VAC
F1
Fig. 22. Power supply via a separate transformer
Powering Field Devices via Panel Bus I/O Module
24 V actuator connected to, e.g., an analog output module
Field device located max. 100 m from the analog output
module
Y (0...10 Vdc)
24 V0
230 VAC
24 VAC
max. 100 m
CLIOP822A
73
74
1...8
GND
Y
24 VAC
11...18
F1
F2
Fig. 23. Power supply via Panel Bus I/O Module
Lightning Protection
Please contact your local Honeywell representative for
information on lightning protection.

Table of Contents

Related product manuals