EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
5 EN1Z-1005GE51 R0216
Bus and Port Connections
Overview
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet!
Disconnect the power supply before making connections
to or removing connections from terminals of the
EAGLEHAWK controller or Panel Bus I/O modules.
Do not reconnect the power supply until you have
completed installation.
It is prohibited to power the EAGLEHAWK controller with
the same transformer used to power other controllers or
devices (e.g., the PW M-Bus Adapter).
Observe the rules regarding electrostatic discharge.
24 25 26 27 28 29 30 31 32
24V-0
24V~
1
6 7
4
5
GND1
485-1+
485-1-
n.a.
n.a.
GND2
485-2+
485-2-
n.a.
2
J1 J8
1
8
2
3
RS232
RS485-1
END
BIAS
MID
9
Fig. 2. Top view
1
8
3
J1 J8
END
BIAS
MID
2
Fig. 3. Side view
Legend
1 RS232 / RJ45 socket (for connection of M-Bus and
other RS232-based protocols; factory debugging)
2 USB 2.0 Host Interface (for connection of the IF-LON);
max. 500 mA, high speed
3 Ethernet / RJ45 socket (for BACnet IP communi-
cation); 10/100 Mbit/s; 1 "link" LED and 1 "activity"
LED
4 RS485-1* (isolated; for BACnet MS/TP, Panel Bus, or
Modbus RTU communication)
5 RS485-2* (non-isolated; for BACnet MS/TP, Panel
Bus, or Modbus RTU communication)
6 LEDs
7 USB 2.0 Device Interface (for connection to COACH
AX
web browsers, and 3
rd
-party touch panels)
8 Three-position slide switch (for setting bias and
termination resistance of RS485-1)
9 Future functionality
*Modbus RTU Master/Slave communication is possible on
either or both of the two RS485 interfaces.
WARNING
Risk of electric shock or equipment damage!
It is prohibited to connect any of the RJ45 sockets of the
EAGLEHAWK controller to a so-called PoE-enabled device
("Power over Ethernet").
RS232 / RJ45 Socket
Via its RS232 / RJ45 socket, the EAGLEHAWK controller can
be connected (using an XW586 cable) to a PW M-Bus
Adapter and thus to M-Bus networks. See also section "M-
Bus Connection" on pg. 25.
RS232-RJ45 SOCKET
J1 J8
END
BI
A
S
MID
Fig. 4. RS232 / RJ45 socket
USB 2.0 Host Interface
Via its USB 2.0 Host interface, the EAGLEHAWK controller
can be connected to, e.g., the IF-LON External Interface
Adapter and thus to L
ONWORKS networks. Max. 500 mA, high
speed. See also section "LonWorks Communications" on pg.
19.