EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1005GE51 R0216 26
M-Bus Connection Procedure
1. Install the PW M-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the
underside of the PW and pry downward to loosen clamp
until the unit snaps onto the rail.
1
2
3
DIN RAIL
Fig. 42. Mounting of PW (PW3 shown here)
2. Connect the M-Bus devices to the PW M-Bus Adapter.
All M+ and M- terminals are connected in parallel in the
PW M-Bus Adapter.
XW586
INSERT
METER-BUS
WIRES
INSERT POWER
SUPPLY WIRES
Fig. 43. PW M-Bus adapter connections
3. Connect the PW M-Bus Adapter to the RS232 / RJ45
socket of the EAGLEHAWK using the XW586 cable.
J1 J8
END
BIAS
MID
XW586
EAGLEHAWK
RS232 / RJ45
SOCKET
M-BUS
DEVICE
Fig. 44. Connecting the EAGLEHAWK to the PW M-Bus
adapter
4. Connect 24 V power to the M-Bus Adapter.
WARNING
Risk of electric shock or equipment damage!
It is prohibited to power the EAGLEHAWK controller with
the same transformer used to power other controllers or
devices (e.g., the PW M-Bus Adapter).
PANTHER,
TIGER, LION,
etc.
PANTHER,
TIGER, LION,
etc.
PW3, PW20,
PW60, etc.
PW3, PW20,
PW60, etc.
!
CLAXEHxxx
CLAXEHxxx
CLAXEHxxx
CLAXEHxxx
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
24 VAC
0 V
24 VAC
0 V
24 VAC
0 V
24 VAC
0 V
Fig. 45. Connecting power to the PW M-Bus adapter