EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1005GE51 R0216 26
M-Bus Connection Procedure
1. Install the PW M-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the
underside of the PW and pry downward to loosen clamp
until the unit snaps onto the rail.
1
2
3
DIN RAIL
Fig. 42. Mounting of PW (PW3 shown here)
2. Connect the M-Bus devices to the PW M-Bus Adapter.
All M+ and M- terminals are connected in parallel in the
PW M-Bus Adapter.
XW586
INSERT
METER-BUS
WIRES
INSERT POWER
SUPPLY WIRES
Fig. 43. PW M-Bus adapter connections
3. Connect the PW M-Bus Adapter to the RS232 / RJ45
socket of the EAGLEHAWK using the XW586 cable.
J1 J8
END
BIAS
MID
XW586
EAGLEHAWK
RS232 / RJ45
SOCKET
M-BUS
DEVICE
Fig. 44. Connecting the EAGLEHAWK to the PW M-Bus
adapter
4. Connect 24 V power to the M-Bus Adapter.
WARNING
Risk of electric shock or equipment damage!
► It is prohibited to power the EAGLEHAWK controller with
the same transformer used to power other controllers or
devices (e.g., the PW M-Bus Adapter).
PANTHER,
TIGER, LION,
etc.
PANTHER,
TIGER, LION,
etc.
PW3, PW20,
PW60, etc.
PW3, PW20,
PW60, etc.
!
CLAXEHxxx
CLAXEHxxx
CLAXEHxxx
CLAXEHxxx
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
24 VAC
0 V
24 VAC
0 V
24 VAC
0 V
24 VAC
0 V
Fig. 45. Connecting power to the PW M-Bus adapter