EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1005GE51 R0216 22
Connecting EAGLEHAWK via its RS485-2 Interface to a BACnet MS/TP Bus
With regards to Fig. 35 and Fig. 36, please note the following:
NOTE: Always power each EAGLEHAWK controller and the connected BACnet MS/TP modules via separate transformers.
NOTE: For “L,” see section “RS485 Standard” on pg. 8.
NOTE: If any devices are not electrically isolated, signal ground connection is recommended. See section “RS485 Standard”
on pg. 8).
NOTE: Between devices equipped with non-isolated RS485 bus interfaces, potential differences of max. ±7 V are allowed.
Further, this bus should not extend beyond a single building.
Example 1: Single EAGLEHAWK Controller and Connected BACnet Modules (with inserted termination
resistor)
1 2
24V~
24~0
2930 31
GND-2
GND-2+5V
RS485-2 (+) RS485-2 (-)
550 OHM 550 OHM130 OHM
F1
230 V
24 V
R
T
BACnet
Module #2
RS485 +
RS485 -
GND
BACnet
Module #3
BACnet
Module #4
BACnet
Module #N-1
BACnet
Module #N
RS485 +
RS485 +
RS485 +
RS485 +
RS485 -
RS485 -
RS485 -
RS485 -
GND
GND
GND
GND
L
BACnet
Module #1
END
BI
A
S
MID
NO EFFECT ON RS485-2
*CONNECT GND, IF AVAILABLE.
120 OHM
EAGLEHAWK
Fig. 35. Connection of a single EAGLEHAWK controller via its RS485-2 interface to a BACnet MS/TP Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.
Example 2: Multiple EAGLEHAWK Controllers and Connected BACnet Modules
1 12 2
24V~
24V~
24~0
24~0
29 2930 3031 31
GND-2 GND-2
GND-2 GND-2+5V +5V
RS485-2 (+) RS485-2 (+)RS485-2 (-) RS485-2 (-)
550 OHM 550 OHM550 OHM 550 OHM130 OHM 130 OHM
F1 F1
230 V 230 V
24 V 24 V
1 12 2
24V~
24V~
24~0
24~0
24 2425 2526 26
RS485 +
RS485 -
GND
BACnet
Module
RS485 +
RS485 -
GND
F1 F1
230 V 230 V
24 V 24 V
L
GND-1 GND-1
+5V
ISO
+5V
ISO
RS485-1 (+) RS485-1 (+)RS485-1 (-) RS485-1 (-)
47 kOHM 47 kOHM
END
BI
A
S
MID
MID
END
BI
A
S
MID
MID
*CONNECT GND, IF AVAILABLE.
GND-1
47 kOHM
GND-1
47 kOHM
BACnet
Module #1
BACnet
Module #2
BACnet
Module #3
BACnet
Module #N-1
BACnet
Module #N
END
BI
A
S
MID
NO EFFECT ON RS485-2
END
BI
A
S
MID
NO EFFECT ON RS485-2
EAGLEHAWK EAGLEHAWK EAGLEHAWK EAGLEHAWK
Fig. 36. Connection of multiple EAGLEHAWK controllers via their RS485-2 interfaces to a BACnet MS/TP Bus