EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
EN1Z-1005GE51 R0216 28
TROUBLESHOOTING
EAGLEHAWK Controller Troubleshooting
The following LEDs of the EAGLEHAWK controller can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
L1 and L2 LEDs (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of EAGLEHAWK
Table 21. EAGLEHAWK controller power LED
case power LED meaning remedy
1
ON Normal operation No action necessary.
2
OFF
Power supply not OK.
Check power supply voltage.
Check wiring.
If problem persists, replace hardware.
Status LED (red) of EAGLEHAWK
Table 22. EAGLEHAWK controller status LED
case status LED meaning remedy
1
OFF after
power-up
Normal operation. No action necessary.
2
ON con-
tinuously after
power-up
No or invalid firmware, or
No or corrupt application.
Try powering down and then powering up the
EAGLEHAWK controller.
If problem persists, replace hardware.
L1 LED
Table 23. EAGLEHAWK controller bus L1 LED
case bus LEDs meaning remedy
1
ON con-
tinuously after
power-up
Normal operation; this may continue for
several minutes until the platform is running
No action necessary.
2
Flashes
constantly
The platform is running
No action necessary.
3
Dark
Severe software problems.
Contact TAC.
L2 LED
Table 24. EAGLEHAWK controller bus L2 LED
case bus LEDs meaning remedy
1
ON con-
tinuously after
power-up
Station is starting up. It may take several
minutes until the station is ready to
communicate.
No action necessary.
If you are unable to establish communication,
consult "Application Director Output" in COACH
AX
.
2
Dark
Station is not running
Contact TAC.