CLASS 320 METER
47 62-0397-02
41033 2 Float Real power, phase C kW R
41035 2 Float Reactive power, phase A kVAR R
41037 2 Float Reactive power, phase B kVAR R
41039 2 Float Reactive power, phase C kVAR R
41041 2 Float Apparent power, phase A kVA R
41043 2 Float Apparent power, phase B kVA R
41045 2 Float Apparent power, phase C kVA R
41047 2 Float Power factor, phase A % PF R
41049 2 Float Power factor, phase B % PF R
41051 2 Float Power factor, phase C % PF R
41053 2 Float Current, phase A Amps R
41055 2 Float Current, phase B Amps R
41057 2 Float Current, phase C Amps R
41059 2 Float Voltage, line to neutral, phase A-N Volts-N R
41061 2 Float Voltage, line to neutral, phase B-N Volts-N R
41063 2 Float Voltage, line to neutral, phase C-N Volts-N R
41065 2 Float Voltage, line to line, phase A-B Volts-L R
41067 2 Float Voltage, line to line, phase B-C Volts-L R
41069 2 Float Voltage, line to line, phase C-A Volts-L R
41071 2 Float Phase angle, phase A Degree R
41073 2 Float Phase angle, phase B Degree R
41075 2 Float Phase angle, phase C Degree R