DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
11 34-00032—01
Table 7. Sensor Diagnostics.
Table 6. Fault Code Information.
Fault No. Description Corrective Action
1 Internal Communication Fault Replace control
2 Internal Fault Replace control
3 Low 24V Measure 24V (R & C). There may be something in the
system loading the 24V transformer excessively. If voltage
is normal while the fault is currently active, replace the
control.
4 Corrupt Memory Reset configuration options. Replace the control if the fault
persists.
5High Pressure Lockout HPC
opened 3 times on a single
request.
Investigate refrigerant charge
Check indoor coil for blockage
Check outdoor coil for blockage
6 Low Pressure Lockout – LPC
opened 3 times on a single
request.
Investigate refrigerant charge
7 High Pressure Cutout is currently
open
Investigate refrigerant charge
Check indoor coil for blockage
Check outdoor coil for blockage
8 Low Pressure Cutout is currently
open
Investigate refrigerant charge
9 Coil Sensor Open Circuited Check the sensor hasn’t become unplugged.
Check sensor wiring
•Replace sensor
10 Coil Sensor Shorted Check for pinched wires
•Replace sensor
11 Air Sensor Open Circuited Check the sensor hasn’t become unplugged.
Check sensor wiring
•Replace sensor
Note that this fault will only present itself if the sensor opens
after it has been detected. It will be cleared on a reset or power
cycle. Running without an air sensor causes the control to
operate in a timed defrost mode, which may be desired
operation.
12 Air Sensor Shorted Check for pinched wires
•Replace sensor
Display Description
Air sensor open circuit or unplugged
Air sensor shorted
Coil sensor open circuit or unplugged
Coil sensor shorted
A
−−
M37655
A
__
M37656
C
M37658
__