3
Point Remote Gas Sensor User Manual
Specifications
Specifications
Specifications
Power:
(must be E³Point, Class 2 or
limited power source [lps])
Electrochemical sensor: 10-24 VDC, 50 mA
Catalytic: 10-16 VDC, 100 mA
Operating temperature:
-20ºC to 50ºC (-4ºF to 122ºF)
Operating humidity:
15 to 90% relative humidity (non-condensing)
Sensor type:
Electrochemical cell (CO, NO
2
, H
2
S, O
2
); catalytic
(Comb)
Visual indicator:
Amber LED (Tx)
Size (DxWxH):
3.5 x 4.5 x 6.5 cm (1.36 x 1.75 x 2.56 in.)
Weight:
38 g (1.34 oz.)
Detection Ranges and Alarm Levels
Gas Detected
Range
Alarm A
Alarm B
Alarm C
Maximum
CO
Carbon monoxide
0-250 ppm
25 ppm
200 ppm
225 ppm
500 ppm
H S
2
Hydrogen sulfide
0-50 ppm
10 ppm
15 ppm
45 ppm
150 ppm
NO
Nitrogen dioxide
0-10 ppm
0.7 ppm
2 ppm
5 ppm
1000 ppm
O
Oxygen
0-25 %vol
19.5 %vol.
22 %vol.
23 %vol
100 %vol
COMB
Combustibles
0-100 %LEL
25 %LEL
50 %LEL
90 %LEL
100 %LEL
Maximum overrange is the cell exposure to gas concentration that
may result in permanent damage to the cell.
Sensor Overrange
When Interfacing with the E³Point Main Unit
• Sensor overrange occurs whenever the gas concentration reading is
higher than the full scale value, no matter how high the gas
concentration is.
• Overrange Warning state is latched when true. It stays activated
indefinitely and independent of gas concentration reading.
• Refer to the E³Point Network or Standalone manual for a description
of overrange conditions.