ECS Series Manual — P/N 151455:H 2/15/2022 13
Electrical Specifications Installation
3.4 Electrical Specifications
Module Voltage
Standby
Current
*Alarm Current
(fully loaded system)
ECS-50W 25V 120V 60 Hz 350 mA 1100 mA
ECS-50W 25V 240V 50/60 Hz 200 mA 600 mA
ECS-50W 70V 120V 60 Hz 350 mA 1200 mA
ECS-50W 70V 240V 50/60 Hz 200 mA 600 mA
Table 3.1 ECS-50W AC Current Draw
Module Voltage
Standby
Current
*Alarm Current
(fully loaded system)
ECS-125W 25V 120V 60 Hz 300 mA 2200 mA
ECS-125W 25V 240V 50 Hz 250 mA 1250 mA
Table 3.2 ECS-125W AC Current Draw
Module Voltage
Standby
Current
*Alarm Current
(fully loaded system)
ECS-DUAL50W 25V 120V 60 Hz 210 mA 2510 mA
ECS-DUAL50W 25V 240V 50/60 Hz 260 mA 1525 mA
ECS-DUAL50W 70V 120V 60 Hz 210 mA 2650 mA
ECS-DUAL50W 70V 240V 50/60 Hz 260 mA 1600 mA
Table 3.3 ECS-DUAL50W AC Current Draw