ECS Series Manual — P/N 151455:H 2/15/2022 31
Installing the ECS-INT50W ECS Device Installation
4.4.10 Calculating Current Draw and Standby Battery
This section helps you determine the current draw and standby battery needs for your installation (18 ampere hours max. will fit in cabinet).
These capacities have a built-in 20% derating factor. Complete the remaining instructions in Table 4.1.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be housed in the RBB Accessory Battery Cabinet. The system
supports a maximum of 33 AH batteries.
4.5 Installing the ECS-INT50W
This section provides information on how to install the ECS-INT50W for use with the ECS Series products. The ECS-INT50W Internal
Amplifier can fit inside the IFP-300ECS or IFP-2000ECS cabinets. It can also be adapted to fit into the IFP-2100ECS cabinet with the ECS-
AMPMT mounting kit (sold separately). It is used to amplify the audio message for distribution throughout the facility for the Emergency
Communication System.
4.5.1 Board Layout & Mounting
Mounting the ECS-INT50W
1. Remove AC power and disconnect the backup batteries from the main control panel.
2. To mount the ECS-INT50W inside the FACP cabinet below the main board, align the board with the mounting holes and secure the
board to the enclosure with the eight supplied screws.
Device
No. of
Devices
Current Per Device
Standby
Current
Alarm
Current
ECS-50W 25V 1 Standby: 85 mA 85 mA
Alarm: 525 mA 525 mA
ECS-50W 70.7V 1 Standby: 100 mA 100 mA
Alarm: 580 mA 580 mA
ECS-CE4 0 or 1 Standby: 20 mA 20mA
Alarm (All Channels): 180 mA 180 mA
A Current Subtotals: mA mA
Notification Devices Refer to device manual for number of devices and current ratings.
B Current Subtotals: mA mA
C Total current rating of all devices in system (Line B) X 0.001 A A
D Number of standby hours (24 or 60 for NFPA 72) H
E Multiply line C (standby current) and D: Total standby AH AH
F Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours): H
G Multiply line C (alarm current) and F: Total alarm AH
AH
H Add lines E and G (AH = Ampere Hours): Total AH required AH
Table 4.1 Current Draw ECS-50W and ECS-CE4