1. To facilitate wiring, remove the Power Brick assembly from the enclosure by
loosening the two retaining screws and sliding the brick assembly out.
2. Terminate the AC cables at the AC terminal block on the Power Brick module. The
module has polarity markings for Live (L), Neutral (N) and Ground.
3. Ensure that all connections are secure and then slide the module back into the
enclosure and secure it with the retaining screws.
4. Secure all connections and wires and connect the cover-ground connection lug to
the enclosure cover to complete the wiring.
If an AC power option is ordered from the factory, the DC output of the
power conversion module should be pre-wired to the DC terminal block
on the Power Board. Verify that the connection is secure and has the
correct polarity as marked.
Note that AC wiring only applies to the FDAP2, which is FM approved. AC
wiring is not covered under IECEx certification.